Operating Manual PSEN sl restart interlock
22209EN02
7
Installation
WARNING!
Function is overridden due to too short a distance or a foreign body
between safety switch and actuator
Mechanical tolerances or an angular offset can reduce the distance
between safety switch and actuator. As a result, the assured release dis
tance may not be maintained despite the addon module and the safety
gate is detected as closed. This can result in serious bodily injury and
death.
The distance between safety switch and actuator must be at least 15 mm
and may not contain any foreign bodies.
After installation, check that the safety switch detects the safety gate as
open and that the "Safety Gate" LED is extinguished when the addon mod
ule is activated (see chapter entitled "Operation").
}
Attach the side section using the provided socket head cap screws with the correspond
ing spring rings on the safety switch. If you wish to prevent the installation from being
manipulated, replace one of the socket head cap screws with the oneway screw
provided (see diagram).
}
Fasten the screws with a torque setting of 5.5 Nm +/0.5 Nm and protect the screws
from working loose with a threadlocker (e.g. Loctite 2700).
}
Comply with the maximum lateral offset for the actuator, as stated in the operating
manual for the PSENslock.