![Pilz 540303 Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/pilz/540303/540303_operating-manual_1556397009.webp)
PSEN cs1.19n
Operating Manual PSEN cs1.19n
1003269-EN-04
9
State of the outputs:
Actuator in the re-
sponse range
Safety out-
put 12
Safety output
22
LED OSSD1
LED OSSD2
OSSD1
High
Low
OSSD2
Low
High
OSSD1&2
High
High
---
Low
Low
Block diagram
A1
A2
Power
12 22
Receiver
Actuator
OSSD1
Actuator
OSSD1&2
Actuator
OSSD2
Operating distances
On
Off
Legend:
}
S
ao
Assured operating distance:
15 mm
}
S
o
Typical operating distance:
21 mm
}
S
r
Typical release distance: 24 mm
}
S
ar
Assured release distance: 40 mm