PSEN ma1.3a/b-21 VA
Operating Manual PSEN ma1.3a/b-21 VA
1004515-EN-02
11
}
Technical data of the evaluation device must fulfil the requirements in the
of PSEN ma1.3a/b-21 VA
–
Always comply with the max. switching current safety contacts of PSEN ma1.3a/
b-21 VA.
}
Outputs at the evaluation device must only be switched on again when both reed con-
tacts at the safety switch have been opened and closed (partial operation lock)
INFORMATION
Risk time in accordance with DIN EN 60947-5-3
The risk time is made up of the reaction time of the sensor (see
) and the processing and delay times of the evaluation
device (s. operating manual for the relevant evaluation device).
PSENmag
3
1
2
4
5+
6
Evaluation device
Input circuit
Input circuit
Fig.: Dual-channel connection PSEN ma1.3a/b-21 VA to the input circuits of an evaluation device
Examples for connection to Pilz evaluation devices:
1
2
3
4
5+
6
S21
S22
S11
S12
PNOZ s3
PSENmag
brown
white
blue
black