Operation
Operating Manual PSSu E S 2DOR 10(-T)
22047-EN-05
25
7
Operation
7.1
Messages
A module error is displayed via the "Err" LED (see section entitled "Display elements"). It is
signalled to the head module and then entered in the
}
Error stack, with PSSu in system environment A
}
Diagnostic log, with PSSu in system environment B.
of the head module.
The module can detect the following errors:
Error
Explanation
Remedy
Start-up error
Error as the PSSu system starts
up.
Change faulty module.
Configuration error
Incorrect module type configured. The configured hardware registry
does not match the actual hard-
ware registry.
ST communication error
Error in ST communication with
the head module.
Change faulty module.
Bus termination error
There is no end bracket.
Install a terminating plate with in-
tegrated end angle.
Temperature error: too warm (
1
)
Ambient temperature too high:
Error stack entry
Ensure there is sufficient ventila-
tion in the control cabinet or pre-
vent overload.
Temperature error: too hot (
1
)
Ambient temperature too high:
Relay outputs are switched off
Ensure there is sufficient ventila-
tion in the control cabinet or pre-
vent overload.
(
1
) There are two levels of overtemperature.
}
Too warm:
If a module's temperature exceeds a theshold value, the module sends a warning to the
head module. If the temperature drops back below the threshold value, the module
sends an all-clear.
}
Too hot:
If a module's temperature exceeds a further theshold value, the module sends an error
message to the head module and switches off the relay outputs.
}
After the "too hot" message has been received, if the temperature drops back below the
"too warm" theshold value, the relay contacts will close if the head module has set the
status of the outputs to "1".
Further information on PSSu error messages is available in the online help for the PSSuni-
versal Assistant system software.