Installation
Operating Manual PMI v507, PMI v512
1003981-EN-01
17
5.3
Installing the unit
When installing the unit, please note the following:
}
For reasons of stability, the front panel, console or control cabinet should have a wall
thickness of at least 2.5 mm.
}
To avoid a build-up of heat, a distance of a 10 cm/3.94" should be maintained all round
the system.
}
Ensure the information given for the ambient and operating temperatures in the tech-
nical details is observed.
}
Protection type IP65 (PMI v507)/IP66 (PMI v512) is only guaranteed when
–
the fixing screws are tightened as follows: min. 0.3 Nm, max. 0.5 Nm.
–
the gasket is not damaged
–
the wall thickness is at least 2.5 mm.
5.4
Installation
Fig.: Installing the PMI v507