RW
Current Channel of 3
rd
Voltage mapping
2 means 2
nd
forward current
3 means 3
rd
forward current
0x8001 means 1
st
reverse current
0x8002 means 2
nd
reverse current
0x8003 means 3
rd
reverse current
40213
RW
Working status of relay 1
0—1, default 0, remote
0 means remote control
1 means auto alarm
40214
RW
Return time of relay 1
Default 0
0~120 (s)
0 means blocking.
40215
RW
Working status of relay 2
0—1, default 0, remote
0 means remote control
1 means auto alarm
40216
RW
Return time of relay 2
Default 0
0~120 (s)
0 means blocking.
40217
Reserved
60