8.6.2 List of demand data registers
Regist
er
addres
s
Read
/write
attrib
ute
Definition
Data
type
Description
40701
RO
Phase A current demand
UINT16
Calculation factor:
0.001, unit: A
40702
RO
Phase B current demand
40703
RO
Phase C current demand
40704
RO
Phase A active power demand
UINT16
Calculation factor:
0.1, unit: W
40705
RO
Phase B active power demand
40706
RO
Phase C active power demand
40707
RO
Total active power demand low word
LINT32
Calculation factor:
0.1, unit: W
40708
Total active power demand high word
40709
RO
Maximum phase A current demand
UINT16
Calculation factor:
0.001, unit: A
40710
RO
Maximum phase B current demand
40711
RO
Maximum phase C current demand
40712
RO
Maximum phase A active power
Calculation factor: