Pilot Communications PMAC901 Скачать руководство пользователя страница 9

 

8.   

PMAC901 Modbus RTU 

 

Metering Data Registers (F03) 

 

Register 

Address 

Type of 

Register 

Description 

Remarks 

Type of 

Data 

40001 

RO 

EL 

Energy low 16 bit 

40002 

RO 

EH 

Energy high 16 bit 

Total energy, one decimal 

place.  

Unit: kWh 

unsigned 

long  

40003 

RO 

Voltage, two decimal places, 

Unit: V 

unsigned 

int 

40004 

RO 

IL 

Current low 16 bit 

40005 

RO 

IH 

Current high 16 bit 

Current, three decimal 

places. Unit: A 

unsigned 

long 

40006 

RO 

PL 

Active power low 16 bit 

40007 

RO 

PH 

Active power high 16 bit 

Active power, one decimal 

place.  Unit: W 

long 

40008 

RO 

KVAL 

Apparent power low 16 bit 

40009 

RO 

KVAH 

Apparent power high 16 bit 

Apparent power, one 

decimal place. Unit: KVA 

unsigned 

long 

 

 

Parameter Settings 

Register 

Address 

Type of 

Register 

Description 

Remarks 

40201 

RW 

CT ratio 

1~999 

40202 

RW 

Communication address 

1~247 

 40203 

RW 

Baud rate of COM 1 

0 – 4800bps 

1 – 9600bps 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание PMAC901

Страница 1: ...PMAC901 Single Phase Energy Meter Installation Operation Manual...

Страница 2: ...ameter 2 5 Display and Key press Operation 2 5 1 Display Instruction 2 5 2 LED Lights Instruction 2 5 3 Key press Instruction 3 5 4 Parameter Setting 3 6 Connection Modes and Drawing 5 7 Figure and In...

Страница 3: ...of 50Hz or 60Hz three phase alternating current circuit It displays total energy consumption via LCD and is characterized with good reliability compact size light weight specious nice appearance and...

Страница 4: ...EC61000 4 2 Level 4 Radiated immunity test IEC61000 4 3 Level 3 Electrical fast transient burst immunity test IEC61000 4 4 Level 3 Surge immunity test 1 2 50 s 8 20 s IEC61000 4 5 Level 3 Conducted em...

Страница 5: ...elease to enter programming The screen shows 1 1 1 The last two digits 1 means the current cursor position is on units digit 3 Press several times change the units digit to 0 The screen shows 1 0 1 4...

Страница 6: ...twice to enter baud rate menu The screen shows 3 9 6 The number 3 means baud rate setting option The back number 96 means the baud rate is 9600bps The baud rate can be set to 4800bps or 9600bps 2 If...

Страница 7: ...rrent 100A the meter should be connected via external CT When rated current 100A the meter should be connected directly 1 PMAC901 direct connection drawing rated current 100A 1 2 3 4 TEST 485 CMbus 5...

Страница 8: ...6...

Страница 9: ...40005 RO IH Current high 16 bit Current three decimal places Unit A unsigned long 40006 RO PL Active power low 16 bit 40007 RO PH Active power high 16 bit Active power one decimal place Unit W long 4...

Страница 10: ...Zhuhai Pilot Electronics Co Ltd Distributor HRW Limited Hong Kong admin hrw hk Tel 852 2546 7402 Fax 852 2546 7403 http www hrw hk...