Pilot Communications PMAC901 Скачать руководство пользователя страница 5

(PULSE) 

is active pulse output indicating light. It flashes once as soon as there is a pulse output. 

(REV)

 is opposite energy indicating light. This light is on when the active power is reversed. 

 
5.3 Key-press Instruction 
 

      Move left or quit setting. 

      Increase value or select menu. 

    Enter setting or enter menu. 

 
5.4 Parameter Setting 
 

CT Ratio Programming 

Note: When rated current >5A, default CT ratio is 1. 
 

1

In data displaying interface, press

  for 3 seconds and release to enter setting interface. The default first 

setting menu is CT ratio programming. Default display is: 

1-   1

 

The number 

1- 

means CT ratio setting option. The back number

 1

 means the CT ratio is 1. 

The programming range of CT ratio is 1~999. 

2

If the external CT parameter is 800/5, users should program the CT ratio to 160.   

Press 

  quickly and release to enter programming. The screen shows: 

1-  1   .1

 

 

The last two digits 

.1 

means the current cursor position is on units digit. 

3

Press 

 

several times, change the units digit to 0. The screen shows: 

1-  0   .1

 

4

Then press 

  once again, the screen 

shows

:

 

1-    0    .2 

The last digit 

.2 

means current cursor position is on tens digit. 

5

Press 

 

several times,  change the tens digit to 6. The screen shows: 

1-   60   .2

 

 

6

Then press 

  once again, the screen 

shows

:

 

1-    60    .3 

The last digit

 .3 

means current cursor position is on hundreds digit. 

7

Press 

, change the hundreds digit to 1. The screen shows:

 

1-  1 60   .3 

8

Then press 

  to confirm the setting. The last two digits 

.3 

disappear. Quit CT ratio programming. At this 

moment, CT ratio menu shows: 

1-  1 60   

     

 

(9) Press 

  to quit setting interface. 

                                                                   

   

Communication Address Programming

 

1

In data displaying interface, press

  for 3 seconds and release to enter setting interface. The initial menu is 

CT ratio programming. Press 

  once and release, enter communication address programming. The default 

display: 

2-  1  

 

3

Содержание PMAC901

Страница 1: ...PMAC901 Single Phase Energy Meter Installation Operation Manual...

Страница 2: ...ameter 2 5 Display and Key press Operation 2 5 1 Display Instruction 2 5 2 LED Lights Instruction 2 5 3 Key press Instruction 3 5 4 Parameter Setting 3 6 Connection Modes and Drawing 5 7 Figure and In...

Страница 3: ...of 50Hz or 60Hz three phase alternating current circuit It displays total energy consumption via LCD and is characterized with good reliability compact size light weight specious nice appearance and...

Страница 4: ...EC61000 4 2 Level 4 Radiated immunity test IEC61000 4 3 Level 3 Electrical fast transient burst immunity test IEC61000 4 4 Level 3 Surge immunity test 1 2 50 s 8 20 s IEC61000 4 5 Level 3 Conducted em...

Страница 5: ...elease to enter programming The screen shows 1 1 1 The last two digits 1 means the current cursor position is on units digit 3 Press several times change the units digit to 0 The screen shows 1 0 1 4...

Страница 6: ...twice to enter baud rate menu The screen shows 3 9 6 The number 3 means baud rate setting option The back number 96 means the baud rate is 9600bps The baud rate can be set to 4800bps or 9600bps 2 If...

Страница 7: ...rrent 100A the meter should be connected via external CT When rated current 100A the meter should be connected directly 1 PMAC901 direct connection drawing rated current 100A 1 2 3 4 TEST 485 CMbus 5...

Страница 8: ...6...

Страница 9: ...40005 RO IH Current high 16 bit Current three decimal places Unit A unsigned long 40006 RO PL Active power low 16 bit 40007 RO PH Active power high 16 bit Active power one decimal place Unit W long 4...

Страница 10: ...Zhuhai Pilot Electronics Co Ltd Distributor HRW Limited Hong Kong admin hrw hk Tel 852 2546 7402 Fax 852 2546 7403 http www hrw hk...