background image

 
 
 
 

 

 
 

EMS-LTE User Manual 

 

In working mode, the 

device not response 

Modbus command 

Have not set the device ID. Solution: In setting mode, set device ID ---- >Switch 
the device to Run mode. 

After switching panel 

on, not running 

according to parameter 

setting 

After parameter setting, although clicked "Save" in every page, but missed the 
final "Save Setting" in the menu. 
Solution: Back to Set mode ---->Click "Save" Button after setting one 
Page --->After all page set successfully, click "Save Setting" in the menu. 

 

Configurator software interface and running Select card and enter setting 

Note:

 

Please select “Normal SIM Card (Call and SMS)”  

 

 
 
 
 
 
 
 
 
 
 
 

 
Save: 

Click it to save all of the PC Configurator parameters to the EMS-LTE;

 

Import Configuration file: 

Click it to load additional configuration file to the Configurator; 

Export Configuration file: 

Click it to save the present configuration parameters as a profile for next 

EMS-LTE configurating or backup the parameter settings.

 

 

Содержание EMS-LTE

Страница 1: ...EMS LTE User Manual Document No 2022 0001 2 EMS LTE Environmental Monitoring System User Manual Please read this user manual carefully before using the device ...

Страница 2: ...ck events automatically The EMS LTE is design for working in the harsh industrial application environment widely used in a variety of industrial automation security monitoring system automatically measurement and control system BTS monitoring remote data acquisition telemetrically systems automatically control system It can be used as a remote switch remote I O remote smart PLC timer switches The ...

Страница 3: ...fers to EMS LTE and all its accessories Read Instructions Read all the safety and operating instructions before operating the device Retain Instructions Save the safety and operating instructions for future reference Heed Warnings Heed all warnings on the device and in the operating instructions Follow Instructions Follow all operating and maintenance instructions Cleaning Unplug this device from ...

Страница 4: ...k Object and Liquid Entry Never push objects of any kind into this device through openings as they may touch dangerous voltage points or short out parts that could result in a fire or electric shock Be careful not to spill liquid of any kind onto the device Servicing Do not attempt to service this device yourself as opening or removing covers may expose you to dangerous voltage or other hazards Re...

Страница 5: ... 5A 30VDC 5A 250VAC can auto control by timer alarm link and remote control by SMS 6 analog inputs 12bits resolution supports 0 5V 0 20mA 4 20mA output transducers Inbuilt 8G SD card to save up to tens of thousands historical data and events 1 RS485 port support Modbus Master protocol can extend up to 16 Modbus Slave devices Powerful SMS function Threshold high SMS alert SMS set SMS inquiry and SM...

Страница 6: ... 1 USB Port Protocols SMS GPRS MQTT Modbus RTU RS485 1 RS485 Digital Inputs 8 Digital input NC NO type Analog Inputs 6 Analog Inputs 12 bit resolution 0 5V or 0 20mA or 4 20mA Relay Outputs 4 Rated 5A 30VDC 5A 250VAC Power Outputs 2 Port for external device Extend I O Tags Max 320 Memory Capacity Internal 8G SD card inside can save the data for 10000events Temperature range 20 70 C Humidity range ...

Страница 7: ...Arm Disarmed Indicator Arm is ON disarmed is OFF Run EMS LTE running status indicator ON or OFF stands for EMS LTE halted flicks slowly stand for EMS LTE running RS485 When transmitting data by RS485 the LED will flick otherwise it is off Backside Switch Button Definition SIM Card Slot For SIM Card Installation only supports 1 8V 3V SIM Card Power Switch For switch ON or OFF the EMS LTE Upgrade Fo...

Страница 8: ...ed need to switch off on the device 0 V mA The 1st channel of analog input type switch If not use this channel then no matter is upside or downside Switch it to upside stands for the 1st analog input should connect to 0 5V voltage output transducer Switch it to Downside stands for the 1st analog input should connect to 0 20mA or 4 20mA current output transducer Tips The wrong side will cause devic...

Страница 9: ...e 2nd 8th digital input positive electrode GND GND for digital inputs negative electrode ATN Port Connector Definition ATN GSM 3G 4G Antenna connector 50Ohm SMA male USB Port Connector Definition USB USB port for configuration and upgrading firmware and exporting historical data Digital Solid Relay Output Connector Definition Solid Relay inside for outputs Rated Capacity 5A 30VDC 5A 250VAC 0 0 The...

Страница 10: ...EMS LTE User Manual 7 Wiring ...

Страница 11: ...he configurator software Connection Please insert the SIM Card and install the GSM 3G 4G Antenna Switch the DIP Switch to Setup Mode Before Power On the EMS LTE Switch it to upside is Set Mode under this mode the user can use PC Configurator via USB cable to configure the EMS LTE Parameters or Read Parameter settings Notice Please switch it to Downside after you finished the configurations Otherwi...

Страница 12: ...fault is 1234 Then you can enter the configuration page as below Notice If display the below windows then means the EMS LTE connect to the PC failure The reasons are below 1 USB Driver installation failure 2 USB Cable connection is disconnected 3 The DIP Switch in RUN mode not in SET mode 4 The Upgrade Firmware Switch at Load side not at Workside 5 Power Switch switched off or DC Power Connection ...

Страница 13: ...ch mode switch to Set In setting mode Power light normal ON Run light flicks other lights Off After switching panel on only Power light on panel can t work 1 The Upgrade Firmware Switch at Load side not at Work side Solution Switch the power switch to OFF Upgrade switch to Work side Power switch to ON 2 SD card fallout from the slot Solution Shake panel to listen if there is voice or not 3 In upgr...

Страница 14: ...o Set mode Click Save Button after setting one Page After all page set successfully click Save Setting in themenu Configurator software interface and running Select card and enter setting Note Please select Normal SIM Card Call and SMS Save Click it to save all of the PC Configurator parameters to the EMS LTE Import Configuration file Click it to load additional configuration file to the Configura...

Страница 15: ...onfiguration details first to avoid Slaves information missing 3 Easy way to revise parameter Open parametersetting page Click Read button to get device currentvalue Revise and click Save button Click the Save Settings button in the menu 4 Switch the device mode to Run as below otherwise it will not work Upside is Set mode switch to downside is Run mode Please set the device in Set mode and save s...

Страница 16: ... to enter into Armed Mode automatically after disarmed operation This is useful for security protection applications Tips Arm Under this mode any alarm occurrence will send SMS and dial the authorized numbers immediately And execute the programmed I O outputs Disarmed Under this mode alarm occurrence will not send SMS dial the authorized numbers Timer Reporting SMS Content Settings Tick the relate...

Страница 17: ...to this number Relay Switch Tick it stands for while the Digital Solid Relay Output action will send SMS to this number Slave Alarm Tick it stands for the salve tag triggered will send SMS to this number Slave Failure Tick it stands for when slave communication failure alarm verify time arrive will send SMS to this number Digital Output Relay Output Setting This page is to setup the Output paramet...

Страница 18: ...s Close Time Stands for the relay close and last time default 0 second means always close Repeat Times Stands for how many times does this relay should to repeat Interval Time Stands for interval how many seconds then the relay repeats the action again Match with Repeat Times can work as pulse output unit second ON OFF SMS Tick it stands for while the Recovery action will also send SMS to the auth...

Страница 19: ...se output Start Time Stands for from what time this authorized number can dial in to control it End Time Stands for till what time this authorized number cannot dial in to control it Always Stands for this authorized number can dial in to control it all thetime DI Trigger Settings This page is for setting the digital input alarm conditions and usages ...

Страница 20: ...ck the Recovery Alarm when triggered digital input recovery normal will send this SMS content to authorize number Change SMS Under Arm or 24hr status only when digital input choose Change type once action will send this SMS to authorize number Current Status Stands for input s current status Alarm Verify Time Stands for when the digital input Close or Open last time more than this value will be tr...

Страница 21: ...ice Call notification is not the pre set voicemail notification When there is an alarm the EMS LTE will generate a call to the pre configured mobile number The call does not contain any voice The call will cut off immediately once the call is pick up AI Trigger Settings This page is to setup the analog input alarm conditions and analog input parameter AIN can be used for monitoring temperature cur...

Страница 22: ...mum is 80 minimum is 40 and Humidity maximum is 100 minimum is 0 cannot change them High Alarm SMS Under Arm or 24h status once current value higher than threshold high value will send this SMS content to authorized numbers Low Alarm SMS Under Arm or 24h status once current value lower than threshold low value will send this SMS content to authorized numbers Recovery SMS Under Arm or 24h status if...

Страница 23: ...automatically or it with repeat this action according to the interval time Total can program 10 scheduling events Tick it stands for enable this timer event Reminder When GPRS 3G 4G data transmission protocol is Picobox EMS LTE Protocol the periodically auto upload default enable and upload every 5 minutes Tick stands for enable this timer function otherwise is disable Weekly Hour Minute Stands fo...

Страница 24: ...f what happen then what action does the EMS LTE should execute it is a programmable logic event Total can program up to 40 logic events for automatically control purposes Event Stands for if this occurrence Action Stands for then what action does the EMS LTE should execute RS485 Serial Port Setting This page is for setup the serial port parameters Over the RS485 the EMS LTE can be used as Modbus R...

Страница 25: ... longer than this setting value will ensure slave no response Slave failure verity time When RS485 used as Master if no response time between Master and Slave longer than this value will send SMS to authorize number Modbus RTU Slave function When RS485 as Modbus RTU Slave can be connected to HMI SCADA DCS PLC as below EMS LTE I O Register List and function code Read Input Coil Function Code 02 Rea...

Страница 26: ...l value AIN0 value 100 2 RTU AIN1 AIN1 value real value AIN0 value 100 4 RTU AIN2 AIN2 value real value AIN0 value 100 6 RTU AIN3 AIN3 value real value AIN0 value 100 8 RTU AIN4 AIN4 value real value AIN0 value 100 10 RTU AIN5 AIN5 value real value AIN0 value 100 12 13 reserved not work 14 RTU Power 16 Bit Unsigned AB 1 Byte in Modbus protocol External power voltage real value Power value 100 15 2...

Страница 27: ...oring module Smart transducer Diesel generator UPS Accumulator battery monitoring system etc Can mapping register value from Slave to Master these registers can be setup high or low threshold value and NC NO type moreover can enable to send SMS to users once alarm occurrence by the registers if required Adding Slave Extend I O tags or Modbus RTU converter to SMS alarm gate way When RS485 as Modbus...

Страница 28: ...r Modbus RTU protocol function code command for slave reading and writing Slave Register Starting Address The starting register address for slave data reading and writing Reading Register Quantity How many data quantity need to read used for mapping to device register address Mapping Address Start Stand for mapping the slave start register data to the device start mapping address Mapping Address E...

Страница 29: ...emote I O module When reading writing device register 4 7 actually is reading writing 6 9 register of smart meter Slave Settings Connect the slave to device EMS LTE RS485 port Find the slave port communication parameter and register address from user manual Write device RS485 parameter according to slave port communication parameter pls ensure both parameters are same others communication failure ...

Страница 30: ... one slave have multi register then need to add separately according to register type For example Mxxx remote I O module with digital and analog inputs need to add the digital Boolean first then add the analog 16 Bit Right click the line to edit the slave ...

Страница 31: ...ve register address Channel Name Setup channel name alarm recovery send channel name alarm content to authorize number need to tick Slave Alarm function in number setting page Data Type Fixed already chosen when add slave Input Type NO NC optional default NO Choose NO Normal is NO not alarm when read 0 alarm when read 1 Choose NC Normal status is NC not alarm when read 1 alarm when read 0 ...

Страница 32: ... to mapping slave register address Channel Name Setup channel name alarm recovery send channel name alarm content to authorize number need to tick Slave Alarm function in number setting page Data Type Optional according to slave data type ABCDEFG stands for sorting data in the slave register Ratio Real value read register value ratio alarm threshold high low value is read register value ratio But ...

Страница 33: ...nable alarm function Reminder 1 If need SMS Alarm function pls tick Slave Alarm function for authorize number in Number Settings page 2 When 16 Bit used for extend AIN inputs can t convert acquisition ADC value to actual one according to range For example When Mxxx remote I O module extend AIN since Mxxx AIN register value is ADC then device EMS LTE read value is also ADC value But DAM122 AIN valu...

Страница 34: ...vice read its function code for slave data current status to check if set successfully or not Click Save when operate finished then click Save Setting in the menu to save parameter to device Delete Slave Right click the slave which need to delete click the Delete Slave click Save click the Save Settings in the menu as below Step7 ...

Страница 35: ...parameters connect to PICOBOX CLOUD via GPRS 3G 4G Note Please contact your sales representative for more information on package and configuration Historical Record The device inbuilt 8G SD card store alarm and historical records For saving historical records need to set the saving historical records interval time in Periodically Timer page For historical record once it full will automatically rem...

Страница 36: ...S Command List The SMS commands will be used for remote control the EMS LTE are below 1 Commands error return SMS Event Return SMS Content Any incorrect Command SMS Format Error please check Caps Lock in Command 2 External DC Status Event Return SMS Content External DC goes off External DC Power Goes OFF External DC Power Goes ON External DC Power Goes ON 3 Modify Password 4digits default is 1234 ...

Страница 37: ...ol Number max 21digits Return 0 4 or 5 9 separately while setting SMS Command Return SMS Content Setup password A series number T tel number Notice Series number 0 9 Tel1 Tel2 Tel3 13570810254 Tel4 Tel5 Inquiry password A Return all numbers Delete password A series number Return 0 4 or 5 9 numbers 8 Authority User Number to access control authorized number can dial to disarm and open the door SMS ...

Страница 38: ...annel number nnnnnnnn AINx Low xxx High xxx AINy Low xxx High xxx Delete Threshold password AINR channel number DEL Set AIN measurement range password AINM channel number Lxxx Hxxx AINx Min xxx Max xxx Inquiry measurement range password AINM channel number nnnnnnnn AINx Min xxx Max xxx AINy Min xxx Max xxx Delete measurement range password AINM channel number DEL Inquiry AIN Current Value password...

Страница 39: ...put time password DOT Pulse Output Time xxxS Pulse Output password DOP channel number nnnn No SMS Return 13 Set Server Parameter Cannot setup DNS by SMS SMS Command Return SMS Content Set Server IP password IP IPaddress P Com port Server Port Inquiry password IP Delete password IPDEL 14 Set GPRS APN USER NAME PASSWORD SMS Command Return SMS Content Set password AP apn username userpassword APN Use...

Отзывы: