![Piazzetta P958 Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/piazzetta/p958/p958_instructions-for-installation-use-and-maintenance-manual_1554808009.webp)
Install the product in compliance with the recommended safety distances
from heat sensitive or inflammable materials and not inflammable, from
load bearing and other walls and also from wooden elements, furniture,
etc.
In the case of flooring that is heat sensitive or inflammable the floor
must be protected with non-combustible insulating material, e.g. sheets
of steel plate, marble, tiles, etc.
The minimum distances are:
A
10 cm from the wall behind the stove
B
20 cm from the side wall
C
80 cm in the heat radiation area and from the hot air fan
outlet
D
50 cm floor protection
E
30 cm (measured from the inner edge of the door)
F*
5 cm from the flue gas outlet on the rear wall
Connection to the flue must respect minimum safety distances from
heat-sensitive structural components or inflammable materials (wood
panelling, beams or ceilings, etc) shown in figures.
* = Values referred to the use of original Gruppo Piazzetta flue pipes;
if other pipes are used, the safety fire regulations or fire codes of
reference are applicable.
a
Keep any combustible product such as wooden furniture,
curtains, carpets, combustible liquids, etc. well away from the
stove when it is lit (minimum distance 80 cm).
a
It is recommended that greater distances than those indicated
above be left all round the stove to make any necessary work
on the appliance easier.
DT2011553-02
1.8 MINIMUM SAFETy dISTANCES
Heat radiation area
Rear wall
Side wall
Side wall
B
B
A
D C
STOVE
E
E
F*
Floor protection
Fig. 16
MIN. 10 cm
MIN. 5 cm*
MIN. 40 cm
Fig. 17
Fig. 18
a
The pellet stove is not the same as other stoves. It has a forced draught of flue gas by a fan, which keeps the firebox in a vacuum
and the entire flueway slightly pressurised. For this reason the flue must be completely airtight and correctly installed to ensure both
trouble-free operation and user safety.
• The flueway
must be made
by specialised personnel or firms, as outlined below.
• The flue must be installed in such a way as to guarantee that periodic cleaning can be carried out without dismantling any parts whatsoever.
• Pipes should
always
be sealed with silicone (
not cement-based sealants
) or specially adapted gaskets/seals, which retain their strength and
elasticity at high temperatures (250°C), and should be fixed with 3.9 mm ø self-tapping screws.
a
Using the relative pipe clips, fix the flue to the wall so that it does not weigh on the smoke fan.
d
Do not install dampers or valves that could block the passage of flue gas.
d
Do not connect to a flueway into which other appliances (boilers, extractor hoods, etc.) discharge fumes or vapours.
DT2010229-05
1.9 FLUEwAy
H07026300 / DT2000786 – 00
9
English
DT2032225-00
DT2030335-00
DT2032226-00