ISACC units are networked by connecting the
A
terminals together, and the
B
terminals
together. Next, it is necessary to enable a termination on the two units that are located far-
thest apart. This termination is located at pin header P9, located directly above the RS485
terminal block. To enable termination, move the two black jumpers from the off position to
the on position. If only two ISACC units are being networked, enable both. See the follow-
ing diagram:
node 0
node 1
node 3
node 4
node 2
A
B
A
B
A B
A B
A B
Termination
ON
Termination
ON
Five ISACC units networked
After the units are networked, you must determine the node number for each unit. This must
be done so that the each unit is identified in the network. The “master” unit is identified as 0
(zero). See
Chapter 7: PROGRAMMING: “System”
, for information on how to program the
network node number. See
Chapter 7: PROGRAMMING: “Network”
for information on how
to make a network request. See
Chapter 8: C PROGRAMMING
for information on how to
use network information in C programming.
Содержание Sensaphone ISACC
Страница 1: ...Sensaphone ISACC Operator s Manual version 3 49...
Страница 22: ...22 Sensaphone ISACC Instruction Manual...
Страница 52: ...52 Sensaphone ISACC Instruction Manual...
Страница 76: ...76 Sensaphone ISACC Instruction Manual...
Страница 114: ...114 Sensaphone ISACC Instruction Manual...
Страница 120: ...120 Sensaphone ISACC Instruction Manual...
Страница 124: ...124 Sensaphone ISACC Instruction Manual...
Страница 130: ...130 Sensaphone ISACC Instruction Manual...
Страница 132: ...132 Sensaphone ISACC Instruction Manual...
Страница 140: ...140 Sensaphone ISACC Instruction Manual...
Страница 142: ...142 Sensaphone ISACC Instruction Manual...