2
www.UsePhoenix.com • [email protected]
Toll-Free 1-800-533-7533
1 Specifications
Part No.
4028000
Power
230 volt single phase unit
with user selectable 25 or 40 amp draw
Water
344 pints/day (43 Gallons)
Removal
@ AHAM (80°F, 60%)
Blower
900 CFM Process Airflow
300 CFM React Airflow
Operating
-10ºF to 140ºF
Range
Duct
Process/React Inlet: 12” flex duct (optional)
Options
Process Outlet: 8” flex duct or layflat x 2
Reactivation Outlet: 8” flex duct (required)
Warranty
1 year Parts and Service
Dimensions
Machine
Width
26.5”
Height
35”
Depth
45”
Weight
265 lbs
Popular Accessories And Replacement Parts
4020550
24” x 12” x 2” Pleated Media MERV-7
4024750
12” x 25’ Flex Duct
4024935
10” x 250’ Lay-flat Duct
4024440
Kestrel 3000 Multi-Meter
2 Operation
The function of the dehumidifier is to remove moisture (in
the vapor state) from an air stream. This is accomplished
by exposing the air to an adsorbing media (desiccant) in
a sealed air stream (process). After the desiccant has
adsorbed moisture, it is exposed to a second air stream
at an elevated temperature (reactivation). This causes
the moisture to be driven out of the desiccant preparing it
for more moisture adsorption. This process is done on a
continuous basis, providing a constant drying process.
The two air streams (process and reactivation) are separated
by seals, which contact the desiccant media. Figure “A”
illustrates the relationship of the seals and airflow pattern.
The dehumidifier is designed with the two air streams flowing
in opposite directions (counter flow) thereby maximizing the
energy efficiency of the equipment.
Table of Contents
Introduction
.........................................................................1
1. Specifications
................................................................2
2. Operation
......................................................................2
3. Installation Instructions
..................................................3
3.1 Inspection ...............................................................3
3.2 Placing The Machine ................................................3
3.3 Electrical .................................................................3
3.4 Duct Work ...............................................................3
4. Operating Instructions
....................................................3
4.1 Airflow ....................................................................3
4.2 Desiccant Wheel Rotation ........................................3
5. Start-Up
........................................................................3
5.1 Manual Operation ....................................................3
5.2 Automatic Operation ................................................3
5.3 Make-Up Air Vent .....................................................4
6. Controls
........................................................................4
6.1 Control Switch .........................................................4
6.2 High/Low Switch .....................................................4
6.3 Unit Run Light .........................................................4
6.4 Humidistat ..............................................................4
6.5 Electric Reactivation Controls ...................................4
7. Dehumidifier Maintenance Instructions
............................4
7.1 General Maintenance ...............................................4
7.2 Cabinet ...................................................................4
7.3 Filter .......................................................................4
7.4 Fan and Motor .........................................................4
8. Drive Motor
...................................................................5
8.1 Rotor Drive Belt .......................................................5
8.2 Seals ......................................................................5
8.3 Desiccant Media......................................................5
9. Dehumidifier Service Instructions
....................................5
9.1 Removing Desiccant Rotor ........................................5
9.2 Changing Seals .......................................................5
9.3 Installing Seals........................................................5
9.4 Troubleshooting .......................................................6
10. Service Parts
.................................................................7
11. Wiring Diagram
.............................................................8
Warranty
.......................................................................9
Serial No._________________________________________
Purchase Date_________/_________/_________
Dealer’s Name_____________________________________
Read the operation and maintenance instructions carefully before
using this unit. Proper adherence to these instructions is essential
to obtain maximum benefit from your Phoenix 1200 dehumidifier.
• It is designed to be used
INDOORS ONLY
.
• If used in a wet area, plug it into a
GROUND FAULT
INTERRUPTER
.
•
DO NOT
use the Phoenix 1200 as a bench or table.
• It must always be used in the upright position.