Web interface
105752_en_03
PHOENIX CONTACT
35 / 56
The table below provides an overview of possible error codes:
Table 4
-
1
Diagnostic error codes
Error code
Meaning
0000
hex
The block is not active.
8000
hex
The block is active.
C110
hex
The IP address could not be changed/set, error message of “FB_Set_IP_Adress” block.
C120
hex
The IP address could not be read, error message of “FB_Set_IP_Adress” block.
C210
hex
The bus configuration could not be read, error message of “FB_BusStart” block.
The additional error code “ADD ERROR CODE” provides more information on this error message.
ADD ERROR CODE Meaning
0001
hex
“ALARM_STOP” not executed
0002
hex
“CREATE_CONFIGURATION” not executed
0003
hex
“COMPLETE_READ_CONFIGURATION” not executed (device number)
0004
hex
“COMPLETE_READ_CONFIGURATION” not executed (ID code and PD length)
C220
hex
The bus configuration could not be started, error message of “FB_BusStart” block.
The additional error code “ADD ERROR CODE” provides more information on this error message.
ADD ERROR CODE Meaning
0001
hex
“ALARM_STOP” not executed
0002
hex
“CONFIRM_DIAGNOSTICS” not executed
0003
hex
“CONTROL_PARAMETERIZATION” not executed
0004
hex
“INITIATE_LOAD_CONFIGURATION” not executed
0005
hex
“TERMINATE_LOAD_CONFIGURATION” not executed
0006
hex
“CONFIRM_DIAGNOSTICS” not executed
0007
hex
“ACTIVATE_CONFIGURATION” not executed
0008
hex
“START_DATA_TRANSFER” not executed
C340
hex
Error when comparing the two bus systems (master only), error message of “FB_Connection” block.
The additional error codes “ADD ERROR CODE” provide more information on this error message.