Description of I/O extension modules
3827_en_B
PHOENIX CONTACT
ERR LED
The red ERR LED indicates the error status.
3.1.5
Setting the I/O-MAP address
Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline
wireless system is addressed using the I/O-MAP address. You can assign a maximum of
01 ... 99 addresses to the I/O extension modules in the entire wireless network.
3.1.6
Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of six data words. For additional
information, please refer to Section 3.1, “RAD-AI4-IFS - analog extension module with four
OFF
No error
Flashing
Slow (1.4 Hz)
I/O-MAP address changed
Fast (2.8 Hz)
No bus communication
ON
Critical internal error
Table 3-3
Setting the I/O-MAP address for the RAD-AI4-IFS
Thumbwheel
setting
Description
01 ... 99
I/O-MAP address
00
Delivery state
**, 1* ... 9*
Setting not permitted
*1 ... *9
Interface System slave address, for use with other Interface System
(IFS) master devices
I/O module
Module type
ID
Number of
registers
Address area
Function code
RAD-AI4-IFS
20
hex
06
hex
30xx0 ... 30xx5
fc 04