RAD-AI4-IFS - analog extension module with four
inputs
The analog RAD-AI4-IFS I/O extension module can process up to four input signals
between 0/4 mA ... 20 mA. All inputs are electrically isolated from one another, from the
supply voltage, and from the electronics.
A supply voltage of 12 V DC, minimum, is available at the PWR
1
connection terminal block
for passive sensors (see Figure 3-1, item 1).
3.1.1
Structure
Figure 3-1
RAD-AI4-IFS structure
Item
Designation
1
Analog input 2 for 2-, 3-, 4-wire measuring transducers
2
Analog input 1 for 2-, 3-, 4-wire measuring transducers
3
DIP switches for configuring the analog inputs (current/voltage input)
4
White thumbwheel for setting the I/O-MAP address
5
Connection option for DIN rail connector
6
DIN rail
7
Metal foot catch for DIN rail fixing
8
Analog input 3 for 2-, 3-, 4-wire measuring transducers
9
Analog input 4 for 2-, 3-, 4-wire measuring transducers
10
ERR status LED, red (communication error)
11
DAT status LED, green (bus communication)
12
PWR status LED, green (supply voltage)
IO-MAP
RAD-AI4-IFS
PW
R
DAT
ER
R
1
2
3
4
OFF
ON
DIP-1
8
8
Pw
r
1
Pw
r
2
+I
1
+I
2
-I
1
-I
2
Pw
r
3
Pw
r
4
+I
3
+I
4
-I
3
-I
4
Pw
r
1
Pw
r
2
+I
1
+I
2
-I
1
-I
2
1
2
3
4
5
7
9
12
11
10
8
6
Содержание RAD-900-DAIO6
Страница 16: ...RAD 900 14 138 PHOENIX CONTACT 3827_en_B...
Страница 58: ...RAD 900 56 138 PHOENIX CONTACT 3827_en_B...
Страница 94: ...RAD 900 92 138 PHOENIX CONTACT 3827_en_B...
Страница 98: ...RAD 900 96 138 PHOENIX CONTACT 3827_en_B...
Страница 116: ...RAD 900 114 138 PHOENIX CONTACT 3827_en_B...