QUINT4-PS/12-24DC/24DC/1.3/PT

110258_en_00

PHOENIX CONTACT

26/31

13 Operating modes

Depending on the intended use, the power supply can be 

run in series or parallel operation.

13.1 Series operation

To double the output voltage, connect two power supplies in 

series. Only use power supplies with the same performance 

class and configuration for series operation. If two 24 V DC 

power supplies are connected in series, an output voltage of 

48 V DC is available to supply the loads.
Figure 23

Schematic diagrams in series operation

13.2 Parallel operation

You can connect several power supplies in parallel in order 

to increase the power or to supply the loads redundantly.
Figure 24

Schematic diagram in parallel operation

Observe the following points when carrying out parallel 

connection:

1. Use power supplies of the same type and performance 

class

2. Setting the same output voltages

3. Using the same cable cross sections for wiring

4. Using the same cable lengths for the DC convergence 

point

5. Operating power supplies in the same temperature 

environment

6. When three or more power supplies are connected in 

parallel, each output must be protected (e.g., with 

circuit breakers or decoupling modules)

+

-

+

-

-48 V

+

-

+

-

-24 V

+24 V

+

-

+

-

+48 V

+

I

N

+

I

N

+

+

Σ

= I

N

Содержание QUINT4-PS/12-24DC/24DC/1.3/PT

Страница 1: ...power dissipation Technical data short form Input voltage range 12 V DC 24 V DC 25 33 Mains buffering typ 19 ms 24 V DC Nominal output voltage UN 24 V DC Setting range of the output voltage USet 24 V...

Страница 2: ...Ordering data 3 4 Technical data 4 5 Safety and installation notes 13 6 High voltage test HIPOT 14 7 Structure of the power supply 15 8 Mounting removing the power supply 18 9 Device connection termi...

Страница 3: ...1 Multi channel electronic circuit breaker for protecting four loads at 24 V DC in the event of overload and short circuit With electronic locking of the set nominal currents For installation on DIN r...

Страница 4: ...current limitation 1 6 A Inrush current integral I2 t typ 0 1 A2 s Input fuse fast blow internal 15 A During the first few microseconds the current flow into the filter capacitors is excluded The SCC...

Страница 5: ...0 0 25 0 50 0 75 1 00 1 25 1 50 1 75 2 00 IOut A 1 1 2 UIn 12 V DC UOut 24 V DC UIn 24 V DC UOut 24 V DC 2 Input connection data Connection method Push in connection Conductor cross section rigid 0 5...

Страница 6: ...series yes Feedback voltage resistance 35 V DC Protection against overvoltage at the output OVP 32 V DC Rise time typical 1 s UOUT 10 90 Output connection data Connection method Push in connection Co...

Страница 7: ...40 C 1 3 A 320000 h 30 C The expected service life is based on the capacitors used If the capacitor specification is observed the specified data will be ensured until the end of the stated service lif...

Страница 8: ...eration refers to IEC 61010 surrounding air temperature Ambient temperature start up type tested 40 C Ambient temperature storage transport 40 C 85 C Max permissible relative humidity operation 95 at...

Страница 9: ...MC requirements power plant EN 61850 3 EN 61000 6 5 Approvals UL UL Listed UL 61010 1 CAN CSA C22 2 No 61010 1 12 UL Listed UL 61010 2 201 CAN CSA C22 2 No 61010 2 201 18 UL 121201 CSA C22 2 No 213 17...

Страница 10: ...0 6 1 residential EN 61000 6 2 industrial and EN 61000 6 5 power station equipment zone IEC EN 61850 3 energy supply CE basic standard Minimum normative requirements of EN 61000 6 2 CE immunity for in...

Страница 11: ...A Criterion A Power frequency magnetic field EN 61000 4 8 50 Hz 60 Hz 30 A m 16 67 Hz 50 Hz 60 Hz 100 A m 60 s not required 50 Hz 60 Hz 1 kA m 3 s not required 0 Hz 300 A m DC 60 s Comments Criterion...

Страница 12: ...l 1 MHz 1 kV Test Level 2 asymmetrical Signals 1 MHz 0 5 kV Test Level 2 symmetrical 1 MHz 0 5 kV Test Level 2 symmetrical 1 MHz 1 kV Test Level 2 asymmetrical 1 MHz 1 kV Test Level 2 asymmetrical Com...

Страница 13: ...re the correct size and have sufficient fuse protection For the connection parameters for wiring the power supply such as the required stripping length with and without ferrule refer to the technical...

Страница 14: ...higher Routine manufacturing tests are inspected regularly by a certification authority 6 3 High voltage dielectric test performed by the customer Apart from routine and type tests to guarantee electr...

Страница 15: ...l block output voltage Output DC 3 Accommodation for cable binders 4 Integrated snap on foot for carrier rail mounting 5 QR code web link 6 Connection terminal block input voltage Input 7 Signaling DC...

Страница 16: ...keep out areas in mm Nominal output capacity Spacing mm a b c 50 0 30 30 50 5 30 30 If adjacent components are active and the nominal output power 50 there must be lateral spacing of 15 mm 99 b c 22 5...

Страница 17: ...current limitation Switching transistor and main transmitter electrically isolating Secondary rectification and smoothing Filter Optocoupler electrically isolating Additional regulatory protection ag...

Страница 18: ...he integrated snap on foot audibly latches into place B 3 Check that the power supply is securely attached to the DIN rail Figure 7 Snapping the power supply onto the DIN rail 8 2 Removing the power s...

Страница 19: ...onnection wiring is attached safely and securely without damaging the connection wiring Figure 10 Secure connection wiring with cable binder Shorten the excess length of the cable ties Then check agai...

Страница 20: ...al data section Protection Figure 12 Pin assignment for DC supply voltage DC applications require upstream installation of a fuse that is permitted for the operating voltage 9 3 Output By default the...

Страница 21: ...This ensures that sufficient reserve energy is available overdimensioning of the power supply is not necessary For system extension With the static boost up to 125 of the nominal output power is avail...

Страница 22: ...ed recovery time tPause at the maximum dynamic boost current IDyn Boost based on the following values IBase Load Duration of the boost current tDyn Boost Ambient temperature 40 C or 60 C 11 2 1 Recove...

Страница 23: ...c output current IDyn Boost of 2 6 A increases for 2 s tDyn Boost After a recovery time tPause of 6 s the dynamic boost is available once again Figure 18 Example recovery time for 40 C 1 8 5 4 3 6 7 2...

Страница 24: ...h in position 50 75 or boost 100 In each of these switch positions the output power POut is monitored When the set threshold is exceeded the yellow LED lights up POut PThr and the signal output SIG sw...

Страница 25: ...alled in protected areas and has direct connections to other areas must satisfy the immunity criteria Use Phoenix Contact surge protection Order No 2905223 when you are using signal connection types p...

Страница 26: ...ies operation 13 2 Parallel operation You can connect several power supplies in parallel in order to increase the power or to supply the loads redundantly Figure 24 Schematic diagram in parallel opera...

Страница 27: ...ematic diagram redundant operation with diode Certain specifications apply in redundancy operation with regard to the configuration of the keepout areas In redundancy operation the power supplies are...

Страница 28: ...output more than the nominal power for a sustained period Figure 27 Output power depending on the ambient temperature 14 2 Installation height The power supply can be operated at an installation heigh...

Страница 29: ...hould be mounted horizontally for heat dissipation reasons input connection terminal blocks facing downward Please observe the derating for any mounting other than the normal mounting position Reduce...

Страница 30: ...QUINT4 PS 12 24DC 24DC 1 3 PT 110258_en_00 PHOENIX CONTACT 30 31 14 3 3 Rotated mounting position 180 Z axis 14 3 4 Rotated mounting position 270 Z axis 0 1 2 13 2 0 1 2 13 2...

Страница 31: ...S 12 24DC 24DC 1 3 PT 110258_en_00 31 31 PHOENIX CONTACT GmbH Co KG 32823 Blomberg Germany phoenixcontact com 14 3 5 Rotated mounting position 90 X axis 14 3 6 Rotated mounting position 270 X axis 0 1...

Отзывы: