Mounting
108366_en_01
PHOENIX CONTACT
The values of the switching distances apply under the following conditions:
–
Center offset of m = 0 with regard to arrow alignment
–
Measured on plastic mounting surface
–
Without influence from surroundings and mounting surface
Table 3-1
Minimum distances and switching distances
Actuation position
Travel
direction
Minimum dis-
tance in X direc-
tion
Switching distances with regard to respective
travel direction
X direction
-
Typical switch-on distance
13 mm, typical
Assured operation distance S
ao
Position A:
10 mm
Position B:
9 mm
Switching hysteresis
1 mm, minimum
2 mm, typical
Assured release distance S
ar
20 mm, maximum
Repeat accuracy
≤
10 %
Y direction
7 mm
Minimum distance
between the sensor and
actuator in the X direc-
tion
Typical switch-on distance
±9 mm, typical
Assured operation distance S
ao
At 7 mm distance between the sensor and
actuator in the X direction
Position A:
±6 mm
Position B:
±5 mm
Switching hysteresis
1 mm, minimum
2 mm, typical
Assured release distance S
ar
±11 mm, maxi-
mum
Repeat accuracy
≤
10 %
Z direction
-
Typical switch-on distance
±12 mm, typical
Assured operation distance S
ao
At 6 mm distance between the sensor and
actuator in the X direction
Position A:
±7 mm
Position B:
±15 mm
Switching hysteresis
1 mm, minimum
2 mm, typical
Assured release distance S
ar
+Z direction:
23 mm, maximum
-Z direction:
32 mm, maximum
Repeat accuracy
≤
10 %
A
B
+Z
-Z
X
Y