MINI MCR-SL-UI-UI
101945_en_05
PHOENIX CONTACT
4
4
Technical data
Input
Configurable/programmable
Yes, preconfigured
Voltage input signal
0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Max. voltage input signal
30 V
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. current input signal
50 mA
Input resistance of voltage input
Approx. 100 k
Ω
Input resistance current input
Approx. 50
Ω
Output
Voltage output signal
0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Max. voltage output signal
Approx. 12.5 V
Non-load voltage
Approx. 12.5 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal
28 mA
Configurable/programmable
Yes, preconfigured
Short-circuit current
Approx. 22 mA
Load/output load voltage output
≥
10 k
Ω
Ripple
< 20 mV
PP
(at 500
Ω
)
Load/output load current output
< 500
Ω
(at 20 mA)
Supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN,
Order No. 2869728) can be used to bridge the supply voltage. It can be snapped
onto a 35 mm DIN rail according to EN
60715))
Max. current consumption
< 19 mA (Current output, at 24 V DC incl. load)
< 9 mA (Voltage output, at 24 V DC incl. load)
Power consumption
< 450 mW (Current output)
< 200 mW (Voltage output)
General data
Limit frequency (3 dB)
Approx. 100 Hz
Maximum transmission error
≤
0.1 % (of final value)
< 0.4 % (Without adjustment)
Temperature coefficient, typical
< 0.002 %/K
Maximum temperature coefficient
< 0.01 %/K
Step response (10-90%)
Approx. 3.2 ms
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Mounting position
Any
Degree of protection
IP20
Pollution degree
2
Rated insulation voltage
50 V AC/DC