8

Adjustment

A potentiometer is located underneath the cover; this is used 

for fine adjustment of the analog signals once the configura-

tion of the DIP switches has been modified.

The module is adjusted via its output final value:

Connect the calibration source to the input of the isolating 

amplifier and specify the final value of the set input signal.

Use the potentiometer to set the exact final value of the 

set output signal.

9

Connection/application example

Figure 6

Example application

Once the configuration of the DIP switches has 

been modified, the potentiometer allows the 

accuracy to be increased from < 0.4% to < 

0.1%.

0...20mA

24V

0...10V

24V

MINI MCR-SL-UI-UI

5

1

2

3

4

6

7

8

GND3

GND1

IN

GND2

OUT

UB+

UB+

GND3

Control system

Level gauge

Mains voltage

Содержание MINI MCR-SL-UI-UI

Страница 1: ...es or in conjunction with the DIN rail connector Please refer to the section titled Power supply for more information Features Configurable 3 way isolating amplifier Input and output signal range conf...

Страница 2: ...data 4 5 Safety regulations and installation notes 6 5 1 Installation notes 6 5 2 Installation in the Ex area zone 2 6 6 Installation 7 6 1 Connection notes 7 6 2 Structure 7 6 3 Block diagram 7 6 4...

Страница 3: ...consumption of up to 2 A MINI MCR SL PTB 2864134 1 MCR power terminal block for supplying several MINI Analog modules via the T connector with spring cage connection maximum current consump tion of u...

Страница 4: ...e 20 mVPP at 500 Load output load current output 500 at 20 mA Supply Nominal supply voltage 24 V DC Supply voltage range 19 2 V DC 30 V DC The T connector ME 6 2 TBUS 2 1 5 5 ST 3 81 GN Order No 28697...

Страница 5: ...ctor cross section stranded 0 2 mm 2 5 mm 0 2 mm 2 5 mm Stripping length 12 mm 8 mm Ambient conditions Ambient temperature operation 20 C 65 C Ambient temperature storage transport 40 C 85 C Conforman...

Страница 6: ...N 60529 of the device is intended for use in a clean and dry environ ment Do not subject the device to any load that exceeds the described limits The device is not designed for use in atmospheres with...

Страница 7: ...used to supply several modules from the mains MINI SYS PS 100 240AC 24DC 1 5 Order No 2866983 Potentially explosive areas MINI PS 100 240AC 24DC 1 5 EX Order No 2866653 NOTE electrostatic discharge Th...

Страница 8: ...wires The MINI MCR SL UI UI is available with two types of con nection Screw terminal blocks MINI MCR SL UI UI Spring cage terminal blocks MINI MCR SL UI UI SP Screw connection Figure 4 Screw connect...

Страница 9: ...N off ON ON ON off off off 2 10 V ON off ON off off off off off 0 5 V ON ON off ON ON off off off 1 5 V ON ON off off off off off off 0 5 V 0 20 mA off off off off off off ON off 4 20 mA off off off o...

Страница 10: ...value Connect the calibration source to the input of the isolating amplifier and specify the final value of the set input signal Use the potentiometer to set the exact final value of the set output s...

Отзывы: