Process data and status information

108147_en_00

PHOENIX CONTACT

29 / 44

5.4

Device access locks

The device supports three different device access locks. All device access locks are inac-

tive in delivery state and after the "Reset default settings" system command is carried out.

5.5

Data storage (IO-Link data storage)

The device supports the data storage function of IO-Link standard 1.1. The data storage ob-

jects include the nominal currents, the setting of channels after voltage reset, and the pro-

gramming locks for the channels.

36057

dec

8CD9

hex

Total current switch off OUT2

Warning

Single event

Total current switch off trigger: 

OUT2 carried maximum current

36058

dec

8CDA

hex

Total current switch off OUT3

Warning

Single event

Total current switch off trigger: 

OUT3 carried maximum current

36059

dec

8CDB

hex

Total current switch off OUT4

Warning

Single event

Total current switch off trigger: 

OUT4 carried maximum current

Table 5-10

Events

Event code

Designation

Type

Mode

Description

Table 5-11

Device access locks

Device access lock

Effect

Data storage lock

Parameter changes are not uploaded in the data storage of 

the IO-Link master.

Local parameterization lock

The nominal currents of the channels can no longer be pro-

grammed via the buttons on the device. Display of the nom-

inal current is still possible by pressing the button for a long 

time. 

The channels can still be switched on and off with the but-

tons.

Local user interface lock

All button functions are deactivated. 

The channel states are not data memory objects and can be changed either acyclically 

per index access or by means of process data outputs (PDout).

Содержание CBMC E4 24DC/1-10A IOL

Страница 1: ...User manual Multi channel electronic device circuit breaker with IO Link interface ...

Страница 2: ...berg Germany phoenixcontact com 108147_en_00 Multi channel electronic device circuit breaker with IO Link interface Designation Order No CBMC E4 24DC 1 4A IOL 2910410 CBMC E4 24DC 1 10A IOL 2910411 User manual This user manual is valid for UM EN CBMC E4 IOL revision 00 ...

Страница 3: ...operating elements 11 3 3 1 Channel LED button 11 3 3 2 Diagnostics and status indicators 12 3 4 Operating modes 13 3 4 1 Independent operation 13 3 4 2 IO Link operation 13 4 Mounting and power supply 15 4 1 Mounting the device circuit breaker 15 4 2 Power supply connection 16 4 3 Connecting the IO Link connection 16 4 4 IODD file 16 5 Process data and status information 17 5 1 Cyclic process dat...

Страница 4: ...CBMC E4 IOL 4 44 PHOENIX CONTACT 108147_en_00 B Appendixes 37 B 1 List of figures 37 B 2 List of tables 39 B 3 Index 41 ...

Страница 5: ...y as well as applicable stan dards and other regulations This symbol indicates hazards that could lead to personal injury There are three signal words indicating the severity of a potential injury DANGER Indicates a hazard with a high risk level If this hazardous situation is not avoided it will result in death or serious injury WARNING Indicates a hazard with a medium risk level If this hazardous...

Страница 6: ...CBMC E4 IOL 6 44 PHOENIX CONTACT 108147_en_00 ...

Страница 7: ...re requirements Table 2 1 Hardware requirements Hardware Description CBMC E4 IOL Multi channel electronic device circuit breaker with IO Link interface for protecting four consumers at 24 V DC in the event of overload and short circuit For order data see Section Ordering data on page 35 IO Link master For order data see Section Ordering data on page 35 IO Link connecting cable For order data see S...

Страница 8: ...CBMC E4 IOL 8 44 PHOENIX CONTACT 108147_en_00 ...

Страница 9: ...perature derating can be found in Section Technical data under Derating on page 34 IO Link connection The integrated IO Link connection according to IO Link standard 1 1 ensures the connec tion to the IO Link master With the help of the IO Link protocol it is possible to receive and send the cyclic and acyclic data of the device circuit breaker see Section 5 Process data and status information The...

Страница 10: ... main function of the device circuit breaker is to protect the consumers and cables con nected on the output side against overload and short circuit Up to 4 load current circuits can be secured at the device circuit breaker In order to be able to fully operate the CBMC E4 IOL a power supply and an IO Link mas ter with upstream control are required Figure 3 2 IO Link with CBMC topology 1 1 CBMC 1 1...

Страница 11: ...button Function Description On Off Actuate the button briefly 2 seconds to switch the channel on and off Programming mode The respective channel of the programming mode is activated by actuating the channel LED button for a longer time 2 seconds This is signaled by a channel LED flashing yellow Now the currently set nominal current can be read out via the flashing sequence displayed on the LED Fur...

Страница 12: ...e 5 second cooldown phase In the case of constant illumination for more than 5 seconds there is a defect in the power path of the CBMC E4 IOL The device has to be replaced in the event of such an error pattern 1 4 on Red The initial voltage is outside the prescribed range of 18 30 V DC Flashing Yellow Channel is in manual programming mode The currently set entered nominal current is output by the ...

Страница 13: ...ge at IN by means of acyclic access The output channels can only be physically switched on however when the voltage at the IN con nection is in the range of the permitted operating voltage The device is automatically in IO Link operation when it is connected to a configured master port An existing connection is signaled by the flashing of the green IO Link LED under the L connection at the termina...

Страница 14: ...CBMC E4 IOL 14 44 PHOENIX CONTACT 108147_en_00 ...

Страница 15: ... DIN rail Removal A standard tool e g a bladed screwdriver with a blade width of 2 5 mm can be used to re move the device circuit breaker Mounting position Mount the device horizontally The ventilation slots should be oriented upward or down ward Maintain a minimum distance of 30 mm on the top and bottom to ensure convection cooling see Figure 4 1 Convection cooling and Figure 4 2 Minimum distance...

Страница 16: ...he vendor and device ID must be entered for some IO Link masters You can find these in the table below In order to comply with UL approval use copper cables that are designed for operating temperatures 75 C Ensure cables are correctly sized for the maximum input and output cur rent It is imperative to connect the negative pole to the IN terminal to ensure self supply Table 4 1 IO Link connection C...

Страница 17: ...y a 0 must be written at the desired bit position for switching off When several channels are switched on concurrently these are switched on sequentially with 100 ms difference Table 5 1 Bit assignment of the PDout data type Byte 0 PDout Valid Flag Reserved Switch channel 4 Switch channel 3 Switch channel 2 Switch channel 1 Bit 23 22 21 20 19 18 17 16 Byte 1 PDout Nominal current channel 1 Nominal...

Страница 18: ...ster Byte 0 PDin Status channel 1 Status channel 2 Status channel 3 Status channel 4 Error channel 1 Error channel 2 Error channel 3 Error channel 4 Bit 63 62 61 60 59 58 57 56 Subindex 1 2 3 4 5 6 7 8 Byte 1 PDin Nominal current channel 1 Nominal current channel 2 Bit 55 54 53 52 51 50 49 48 Subindex 9 10 Byte 2 PDin Nominal current channel 3 Nominal current channel 4 Bit 47 46 45 44 43 42 41 40 ...

Страница 19: ...channel was switched off after an error A 0 means that no error exists Switching on a channel that was switched off by an error re sets its error status to 0 Load current channel The load current at a channel is encoded in one byte The value range 0 255 corresponds with a gradient of 0 1 to the value range of 0 0 A 25 5 A Input voltage The input voltage of the CBMC E4 IOL is encoded in one byte Th...

Страница 20: ...0Chex 0 Device access lock Reserved 2 bytes rw Bit 0 0 0 Data memory lock Bit 1 0 1 0 Local parameterization lock Bit 2 0 1 0 Local user interface lock Bit 3 0 1 0 Reserved Bit 4 15 0 0 16dec 10hex 0 Manufacturer 15 bytes ro 17dec 11hex 0 Manufacturer text Manufacturer URL 22 bytes ro 18dec 12hex 0 Product name 22 bytes ro 19dec 13hex 0 Product ID Order number 7 bytes ro 20dec 14hex 0 Product text...

Страница 21: ...13 Load current OUT1 1 byte 0 25 5 A 0 1 14 Load current OUT2 15 Load current OUT3 16 Load current OUT4 17 Input voltage 1 byte 10 35 5 V 0 1 10 41dec 29hex 0 Process data output PDout 3 bytes ro 64dec 40hex 0 Product range 58 bytes ro 3328dec 0D00hex 0 Channel state after voltage reset Load state from read only memory all channels out 1 byte rw 0 1 0 3329dec 0D01hex 0 Switching state OUT1 4 4 byt...

Страница 22: ...the device access lock of the data memory is inactive System command 128dec The system command allows the controller of the CCBMC E4 IOL to be restarted System command 130dec The system command resets the device to its default settings 3330dec 0D02hex 0 Local program ming lock OUT1 4 4 bytes rw 0 1 0 1 OUT1 1 byte 0 1 2 OUT2 1 byte 0 1 3 OUT3 1 byte 0 1 4 OUT4 1 byte 0 1 3331dec 0D03hex 0 Nominal ...

Страница 23: ...cess data on page 17 Process data from the master to device PDout The process data from the master to device can be retrieved via Index 41dec In the case of read access 3 bytes are returned Product range The product range is located under Index 64dec and stored as CHAR 5 2 2 Device specific parameters State of the channels after voltage reset The setting for the last channel states from the read o...

Страница 24: ... and status indicators on page 12 it is not possible to switch on the channel either per button or via IO Link Acyclic access that should switch on the channels is acknowledged with an error event Table 5 5 Bit assignment of data type Channel state Switching state channel 1 Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 0 0 0 0 0 0 1 0 Switching state channel 2 Byte 1 Bit 7 Bit 6 Bit 5 B...

Страница 25: ...ramming lock Programming lock active inactive channel 1 Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 0 0 0 0 0 0 1 0 Programming lock active inactive channel 2 Byte 1 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 0 0 0 0 0 0 1 0 Programming lock active inactive channel 3 Byte 2 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 0 0 0 0 0 0 1 0 Programming lock active inactive channe...

Страница 26: ...st error is deleted in parallel FIFO principle The values in FIFO have the following meaning Nominal current channel 4 Byte 3 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 0 0 0 1 0 1 0 1 0 1 0 Table 5 8 Error memory Valuedec Indicates 0 FIFO slot empty e g after Reset to the factory settings command 1 Short circuit channel 1 2 Short circuit channel 2 3 Short circuit channel 3 4 Short circuit ...

Страница 27: ... voltages Output voltage channel 1 Byte 0 high Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 Byte 1 low Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 Output voltage channel 2 Byte 2 high Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 Byte 3 low Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 ...

Страница 28: ...off because of short circuit 36018dec 8CB2hex Short circuit switch off OUT3 Warning Single event OUT3 switched off because of short circuit 36019dec 8CB3hex Short circuit switch off OUT4 Warning Single event OUT4 switched off because of short circuit 36032dec 8CC0hex Overload shutdown OUT1 Warning Single event OUT1 switched off because of overload 36033dec 8CC1hex Overload shutdown OUT2 Warning Si...

Страница 29: ...ing Single event Total current switch off trigger OUT3 carried maximum current 36059dec 8CDBhex Total current switch off OUT4 Warning Single event Total current switch off trigger OUT4 carried maximum current Table 5 10 Events Event code Designation Type Mode Description Table 5 11 Device access locks Device access lock Effect Data storage lock Parameter changes are not uploaded in the data storag...

Страница 30: ...CBMC E4 IOL 30 44 PHOENIX CONTACT 108147_en_00 ...

Страница 31: ... Ambient temperature operating 25 C 60 C Ambient temperature storage transport 40 C 70 C Humidity test 96 h 95 RH 40 C Altitude 2000 m Degree of protection IP20 General Flammability rating according to UL 94 V 0 Mounting type DIN rail 35 mm Color Light gray RAL 7035 Protection class III Pollution degree 2 Design DIN rail module one piece 98 90 36 CBMC 1 2 3 4 1 2 L C Q 1 2 IN IN OUT 1 2 3 4 IO Lin...

Страница 32: ...tion Module initialization time 1 6 s Waiting time after switch off of a channel 5 s in the event of overload short circuit Temperature derating 24 A DC at 60 C 28 A DC at 54 C 32 A DC at 47 C 36 A DC at 41 C 40 A DC at 35 C Electric strength 35 V DC max load circuit Contact type Without electrical isolation MTBF IEC 61709 SN 29500 8403361 h at 25 C with 21 load 3067484 h at 40 C with 34 25 load 5...

Страница 33: ...method Push in connection Stripping length 10 mm Conductor cross section solid 0 2 mm 2 5 mm AWG conductor cross section 24 12 Conductor cross section flexible with ferrule with plastic sleeve 0 25 mm 1 5 mm Conductor cross section flexible with ferrule w o plastic sleeve 0 25 mm 2 5 mm Main circuit OUT Connection method Push in connection Stripping length 10 mm Conductor cross section solid 0 2 m...

Страница 34: ...stic sleeve 0 25 mm 1 5 mm Conductor cross section flexible with ferrule w o plastic sleeve 0 25 mm 2 5 mm DC operating voltage 0 V DC 30 V DC DC operating current 100 mA DC IO Link connection Connection method Push in connection Stripping length 10 mm Conductor cross section solid 0 2 mm 1 5 mm AWG conductor cross section 24 16 Conductor cross section flexible with ferrule with plastic sleeve 0 2...

Страница 35: ...s Description Type Order No Pcs Pkt Multi channel electronic circuit breaker with IO Link inter face for protecting four consumers at 24 V DC in the event of overload and short circuit With electronic locking of the set nominal currents For installation on DIN rails Adjustable from 1 A to 4 A CBMC E4 24DC 1 4A IOL 2910410 1 Adjustable from 1 A to 10 A CBMC E4 24DC 1 10A IOL 2910411 1 ...

Страница 36: ...RK X1 2 THERMOMARK S1 1 mounting type adhered lettering field size 10 x 7 mm EML 10X7 R 0816663 1 Equipment marking roll white unmarked can be marked with THERMOMARK ROLL THERMOMARK ROLL X1 THERMOMARK ROLLMASTER 300 600 THERMOMARK X1 2 THERMOMARK S1 1 mounting type adhered letter ing field size 20 x 7 mm EML ESD 20 X 7 R 0830567 1 Axioline E Ethernet device in a plastic housing with 8 IO Link port...

Страница 37: ...n 3 Figure 3 1 CBMC E4 IOL 9 Figure 3 2 IO Link with CBMC topology 10 Figure 3 3 CBMC E4 IOL operating elements 11 Section 4 Figure 4 1 Convection cooling 15 Figure 4 2 Minimum distance 15 Appendix A Figure A 1 Dimensions 31 Figure A 2 Derating 34 Figure A 3 Tripping characteristics 35 ...

Страница 38: ...CBMC E4 IOL 38 44 PHOENIX CONTACT 108147_en_00 ...

Страница 39: ... 17 Table 5 2 Bit assignment of data type CBMC IO Link to master 18 Table 5 3 Acyclic data 20 Table 5 4 Bit assignment of data type State of the channels after voltage reset 23 Table 5 5 Bit assignment of data type Channel state 24 Table 5 6 Bit assignment of data type Local programming lock 25 Table 5 7 Bit assignment of data type Nominal current 25 Table 5 8 Error memory 26 Table 5 9 Bit assignm...

Страница 40: ...CBMC E4 IOL 40 44 PHOENIX CONTACT 108147_en_00 ...

Страница 41: ...ndicators 12 E Error memory 26 I IODD file 16 IO Link data storage 29 M Mounting 15 Mounting location 15 O O Link connection 16 Operating mode independent 13 IO Link 13 P Parameters Device specific 23 IO Link specific 22 Power supply 16 Programming lock 25 R Removal 15 S Status indicators 12 System commands 22 ...

Страница 42: ...CBMC E4 IOL 42 44 PHOENIX CONTACT 108147_en_00 ...

Страница 43: ... products in your specific application in particular with regard to observing the applicable standards and regulations All information made available in the technical data is supplied without any accompanying guarantee whether expressly mentioned implied or tacitly assumed In general the provisions of the current standard Terms and Conditions of Phoenix Contact apply exclusively in particular as c...

Страница 44: ...ation It can be downloaded at phoenixcontact net products Subsidiaries If there are any problems that cannot be solved using the documentation please contact your Phoenix Contact subsidiary Subsidiary contact information is available at phoenixcontact com Published by PHOENIX CONTACT GmbH Co KG Flachsmarktstraße 8 32825 Blomberg GERMANY Should you have any suggestions or recommendations for improv...

Отзывы: