Description of the CBMC E4 24DC/1-4A+ IOL and CBMC E4 24DC/1-10A IOL
108147_en_00
PHOENIX CONTACT
3.3
Connection and operating elements
Figure 3-3
CBMC E4 ... IOL operating elements
1.
Channel LED button
2.
Protected outputs
3.
24 V DC supply
4.
IO-Link interface
5.
IO-Link LED
3.3.1
Channel LED button
The channel LED button of the CBMC E4 ... IOL is a multi-functional button. The channel
state can be completely influenced with it.
CBMC
1
2
3
4
1
2
L+
C/Q
1
2
IN+
IN-
OUT+
1
2
3
4
1
2
4
3
3
IO-Link
5
L-
Table 3-1
Channel LED button
Function
Description
On / Off
Actuate the button briefly (<2 seconds) to switch the channel on and off.
Programming mode
–
The respective channel of the programming mode is activated by actuating the channel LED
button for a longer time (>2 seconds).
This is signaled by a channel LED flashing yellow.
–
Now the currently set nominal current can be read out via the flashing sequence displayed on
the LED.
–
Furthermore, it is possible to enter a new nominal current by briefly actuating the LED button
repeatedly
For example, 4x actuation for 4 amps.
–
Afterwards, the desired nominal current can be controlled via the LED flashing sequence.
–
By actuating for a longer time (> 2 seconds) the new nominal current for the channel is taken
on.
Содержание CBMC E4 24DC/1-10A IOL
Страница 1: ...User manual Multi channel electronic device circuit breaker with IO Link interface ...
Страница 6: ...CBMC E4 IOL 6 44 PHOENIX CONTACT 108147_en_00 ...
Страница 8: ...CBMC E4 IOL 8 44 PHOENIX CONTACT 108147_en_00 ...
Страница 14: ...CBMC E4 IOL 14 44 PHOENIX CONTACT 108147_en_00 ...
Страница 30: ...CBMC E4 IOL 30 44 PHOENIX CONTACT 108147_en_00 ...
Страница 38: ...CBMC E4 IOL 38 44 PHOENIX CONTACT 108147_en_00 ...
Страница 40: ...CBMC E4 IOL 40 44 PHOENIX CONTACT 108147_en_00 ...
Страница 42: ...CBMC E4 IOL 42 44 PHOENIX CONTACT 108147_en_00 ...