Technical data and ordering data
107709_en_00
PHOENIX CONTACT
Number of supported devices
Max. 63 (per station)
Number of local bus devices that can be connected
Max. 63 (observe current consumption maximum)
NOTE: Electronics may be damaged if overloaded
Note the logical current consumption of each device when configuring an Axioline F station. This is specified
in every module-specific data sheet. The current consumption can differ depending on the individual module.
The permissible number of devices that can be connected therefore depends on the specific station structure.
System limits
PROFINET
Device function
PROFINET controller, PROFINET device
Number of supported devices
Max. 16 (on PROFINET controller)
Specification
Version 2.3
Conformance class
A
Update rate
Min. 32 ms (16 devices)
Min. 32 ms (8 devices)
Min. 16 ms (4 devices)
Min. 8 ms (2 devices)
Min. 4 ms (1 device)
Number of slots
1
Vendor ID
00B0
hex
Device ID
0142
hex
Communications power U
L
feed-in (the supply of the Axioline F local bus U
Bus
is generated from U
L
)
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, ripple included)
Current consumption
Typ. 125 mA (with no I/Os and U
L
= 24 V)
Max. 160 mA (with 2 A at U
Bus
for the I/Os and U
L
= 24 V)
Power consumption
Typ. 3 W (with no I/Os)
Max. 13.2 W (with 2 A load at U
Bus
for the I/Os)
Supply voltage surge protection
Electronic
Supply voltage polarity reversal protection
Electronic
NOTE: Electronics may be damaged if overloaded
Provide external protection for the 24 V part U
L
. If you use a fuse, the power supply unit must be capable of
supplying four times the nominal current of the fuse. This ensures that the fuse trips reliably in the event of a
fault.
Axioline F local bus supply (U
Bus
)
Supply voltage
5 V DC (via bus base module)
Power supply
2 A
Real-time clock
Real-time clock accuracy
1.73 s/day = 20 ppm at 25°C
Power reserve
240 h
Error messages to the higher-level control or computer system
None