Self Diagnostic System Operation – Emergency Light or EXIT Sign Products 

 

Normal Power Up Sequence 
 
At power up the red and green LED indicators will alternately flash for one to two seconds. Next the product will execute a 
“Power Up Quick Test” causing the green LED indicator to flash rapidly. If any faults are detected during the “Power Up Quick 
Test” these will be evident by a flashing red LED indicator.  If the audible diagnostic option has been ordered, the flashing red 
LED will be accompanied by a simultaneous beeping tone. 

(Note: A continuous rapid alternating Red/Green flash with rapid 

beeping tone indicates incorrect voltage applied to input lead. TURN OFF POWER IMMEDIATELY!) 

 
Emergency Operation 
Emergency operation occurs when AC power fails. The product remains in emergency operation until AC power is restored or 
battery capacity is depleted. During emergency operation both red and green LED indicators are disabled. 
 
User Interface 
 

Green LED indicator

 

 

Slow Flash/Continuous ON = AC power present; normal operating condition 

 

Rapid Flash = product performing an automatic or manually initiated diagnostic test 

Red LED indicator 

 

Single Flash = battery fault 

 

Two Flashes = lamp failure (light bar failure – EXIT signs) 

 

Three Flashes = charger fault 

 

Four Flashes = transfer fault 

(If more than one fault condition is present simultaneously, the red LED will flash the indication pattern for each fault 
independently then repeat the cycle.) 
 

Pushbutton Test Switch

 

 

Long Press (longer than 0.5sec) transfers product to emergency operation during time the button is pressed. 

 

Short Press initiates self diagnostic activities as follows: 

 

One Press cancels diagnostic test presently running. 

 

Two Presses starts a one minute diagnostic test. 

 

Three Presses starts a 90 minute diagnostic test. 

 

Four Presses conducts a lamp load calibration (emergency light products only). 

 

Seven Presses initiates a system reset. 

(Note: the microprocessor will allow up to seven, one minute diagnostic tests within the first 24 hours of 
operation. Allow 24 hours of charging before performing any long duration testing.) 
 

Buzzer

 (optional)– Sounds in unison with the flashing red LED if a fault condition is present. Buzzer may be silenced for 

up to 196 hours by a short press of either the test switch or the optional IR remote control device “silence” button. 
Correcting fault condition will cancel fault notification. Lamp failure indication requires a manually activated diagnostic 
test after lamp replacement to cancel notification. 
 

IR Remote Control 

(optional)- is a hand held device that allows remote activation of diagnostic testing and silencing of 

the optional buzzer during fault conditions. 

   

Содержание Symmetry Series

Страница 1: ...o not use this equipment for other than intended use Do not let supply cords touch hot surfaces Do not mount near gas or electric heaters Caution Halogen cycle lamp s are used in this equipment To avoid shattering Do not operate lamp in excess of rated voltage protect lamp against abrasion and scratches and against liquids when lamp is operating dispose of lamp with care Halogen cycle lamps operat...

Страница 2: ...his purpose can be found under the lenses These keyhole slots will accommodate 6 toggle bolts Refer to the sketch above for instructions on removing the lenses Figure 2 STEP 2 see figure 2 Locate 4 pole connector attached to transformer inside unit Remove 6 long extension cable and wire to AC supply as shown Unused black or blue lead must be insulated to prevent shorting If your unit has battery c...

Страница 3: ... Mount unit to wall or ceiling using fasteners supplied with junction box or mount to wall using toggle bolts not provided Pull AC and remote lamp connectors through rectangular knockout and reconnect to matching wire harnesses as shown in step two Reinstall the battery and connect the battery quick disconnect Re secure the Velcro battery strap to secure the battery in place If MR 16 type lamps ha...

Страница 4: ... covers as shown in step 1 Lamp heads may be aimed by grasping them at the base and rotating them to aim at the desired location Lamp head only rotates approximately 135 which is enough to aim in any direction whether mounted on wall or ceiling AC FUSE AND AC OR DC DISCONNECT SWITCH OPTIONS If ordered these options can be found under the right lamp head lens TAMPERPROOFING If ordered install this ...

Страница 5: ...manually initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat the cycle Pushbutton Test Switch Long Press longer than 0 5sec t...

Страница 6: ...ion 200 Franklin Square Drive Somerset NJ 08873 USA Phone 855 486 2216 www philips com luminaires Philips Lighting Canada Ltd 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053520 February 2016 ...

Отзывы: