OPERATING INSTRUCTIONS 

 

(1):   Energize AC power to equipment and check that pilot lamp illuminates red. 
 
(2):   Press test switch and verify pilot lamp turns off and lamp heads illuminate. 
 
(3): Leave AC connected for a minimum of 24 hours before performing any extended testing. Full 
recharge of battery may take up to one (1) week. 
 

NOTE 

 

A.

 

This equipment is provided with a lockout feature whereby connecting battery leads prior to 

energizing AC power will not turn on the emergency lamps. After AC power is energized, the 
emergency lamps will turn on upon AC power failure. 

 

B.

 

This equipment is provided with a low battery disconnect feature which prevents full discharge 

of battery. If the building is to be unoccupied for an extended period and AC is shut off, the battery 
should be disconnected from the charger to prevent damage. 

 

C.

 

The battery in this unit is sealed and requires no maintenance. 

 

SERVICING 

 

(1):   For servicing, remove tamper proof screw (if installed). Then remove cover by inserting a small 
screwdriver or similar tool into the hole in the bottom of the cover and press upward to release locking 
tab. Pull over up and off of unit. 
 
(2):  Remove electronics module from backplate by inserting a flat bladed screwdriver between 
backplate and module and prying module away from backplate. 
 

 

Содержание SV16 Series

Страница 1: ...pering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than intended use Do not let power supply cords touch hot surfaces Do not mount near gas or electric heaters CAUTION Halogen cycle lamp s are used in this equipment To avoid shattering Do not operate lamp in excess of rated voltage pr...

Страница 2: ...ten backplate to junction box using two 8 32x1 1 4 screws supplied For wet location units ensure that the gasket is evenly compressed around perimeter For installation using surface conduit damp location units only Remove necessary mounting knockouts and secure conduit to flange provided at top of backplate Mount backplate to wall using mounting hardware supplied by others Connect AC Harness found...

Страница 3: ...g inside electronics module Connect battery harness to charger board Install electronics module to backplate by hinging together at top and snapping together at bottom Two 6x1 2 screws are provided for further securing electronics module to backplate if so desired Install lamps provided by snapping into ceramic lamp holders on lamp head Attach cover by snapping over electronics module Cover will l...

Страница 4: ...attery leads prior to energizing AC power will not turn on the emergency lamps After AC power is energized the emergency lamps will turn on upon AC power failure B This equipment is provided with a low battery disconnect feature which prevents full discharge of battery If the building is to be unoccupied for an extended period and AC is shut off the battery should be disconnected from the charger ...

Отзывы: