   DLE1210GL Installation Manual Rev H.docx 

 

 

Select A Suitable Location 

This device is designed for indoor use only. 
If  installing  in  an  external  location,  the 
DLE1210GL  must  be  housed  in  a  suitable 
well  ventilated  enclosure.    Choose  a  dry 
location  that  will  be  accessible  after  the 
installation  is  complete.    To  ensure  the 
cooling  system  functions  correctly,  the 
DLE1210GL  should  only  be  mounted 

vertically,  the  right  way  up

.    The 

DLE1210GL  will  generate  heat  when 
operating,  approximately  2  Watts  per  Amp 
of  load,  and  requires  an  air  gap  of  200mm 
on  each  side  and  at  the  top  and  bottom  of 
the device.  This air gap is also required to 
ensure  serviceability  of  the  DLE1210GL 
without 

complete 

removal 

from 

the 

mounting  surface.    This  device  may  emit 
some  mechanical  noise.    Take  this  into 
account  when  deciding  the  mounting 
location. 

 

Fixing the Device 

The  DLE1210GL  has  integral  mounting 
brackets  attached  to  the  enclosure.    The 
brackets  are  designed  to  accommodate  4 
fixing  screws  up  to  8mm  diameter.    The 
DLE1210GL can be fixed to the wall without 
opening  the  cabinet  or  removing  covers.  
Make  sure  no  dust  or  other  debris  enters 
the device during installation.  Do not leave 
the  front  cover  off  for  any  length  of  time.  
Excessive  dust  and  dirt  can  degrade  the 
cooling of internal components. 

 

Allow for Cable Entry 

Supply and load cables enter the enclosure 
at  the  top.    If  these  cables  are  fed  from 
below  the  mounting  position,  they  should 
be  routed  around  the  enclosure  to  enter  at 
the  top.    An  alternative  method  is  to  stand 
the enclosure off from the mounting surface 
by mounting it on a cable tray or a Unistrut 
style  product.    The  cables  can  then  be 
routed  between  the  enclosure  and  the 
mounting  surface,  and  enter  the  enclosure 
via  the  cutout  provided  on  the  mounting 
face.    The  control  cables  enter  at  the 
bottom  of  the  enclosure.    Control  cables 
should  never  be  run  in  the  mains  voltage 
sections of the enclosure.

 

Содержание dynalite DLE1210GL

Страница 1: ...10A Leading Edge Dimmer Installation Manual contents Warning 2 Dimmable Lamps Chart 7 Features 2 Preset Programming Using The Program Key 8 Important Safeguards 2 Hold Down Programming Of Presets 9 Internal View 3 One Touch Button Operation 9 Mounting 4 Troubleshooting 10 Supply Load Cable Connections 5 Specification 10 Connecting Serial Control Cables 6 Useful DyNet Op Codes 11 Hardware Controls ...

Страница 2: ...Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the specified capacity of 10A Loads should be calculated to ensure that the overall ...

Страница 3: ...internal view DLE1210GL Installation Manual Rev H docx 3 For spare parts please call your nearest Dynalite Customer Service Centre and specify DLE1210GL ...

Страница 4: ... DLE1210GL has integral mounting brackets attached to the enclosure The brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DLE1210GL can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the co...

Страница 5: ...individual channel which is 10A To ensure compliance with interference standards the load neutral cables must be individually connected to the neutral link terminals inside the cabinet Never use a common neutral at a remote location Emergency Lighting Connections Connect emergency lighting circuit active to the load side on the circuit breaker for the relevant channel as indicated by the labels ne...

Страница 6: ...r GND one pair paralleled for 12V and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair Paralleled for GND Orange White pair Paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The re...

Страница 7: ...etter performance an electronic HF dimming transformer is recommended The power factor capacitors need to be wired to the supply side of the dimmer Some Dynalite controllers include a supplementary relay contact for control of power factor capacitors If electronic ballasts are not used cabling and controllers should be de rated by approx 60 to allow for reactive current Contact your Dynalite deale...

Страница 8: ...ufacturer s diagram specification Supply 230V 14 50 60Hz Single Phase at 75A or 230 400V 14 50 60Hz 3 Phase Y at 25A per phase Outputs 12 x dimmed outputs leading edge phase control at 10A total device load 75A Protection 12 x 10A 6kA single pole thermal magnetic circuit breakers Regulating Device Triac 600V 40A nom 400A surge Power Conditioning Regulated outputs Over voltage protection Surge prot...