LumaCan™ Phase Cut Dimmer

Cat. No. DRDDP 

INSTALLATION INSTRUCTION

S

ENGLISH

DI-002-DRDDP-00A-X3

WARNINGS

•  TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE 

AND TEST THAT POWER IS OFF BEFORE WIRING!

•  To be installed and/or used in accordance with appropriate electrical codes and regulations.
•  If you are unsure about any part of these instructions, consult an electrician.
•  To avoid electrical overload, total connected lamp load shall not exceed output rating.
•  This equipment permits more than one power supply output source.
•  Do not mount near gas or electric heaters.

CAUTIONS

•  Use this device with copper or copper clad wire only.
•  For indoor applications only.
• 

 

Test all network cables for proper pin-out configuration prior to interconnecting devices and systems.

•  If you are unsure about any part of these instructions, consult an electrician.
•  Save these instructions.

Product Description

The GreenMAX™ DRC Phase Cut Dimmer provides dimming of phase control loads,  

either forward or reverse phase, LumaCAN network connectivity, and full integration 

into Leviton’s GreenMAX DRC system.

Installation

WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!

Wiring Diagrams 

2.

  

Remove/add channel jumpers depending on configuration.

 

DI-002-DRDDP-00A-X3

© 2018 Leviton Mfg. Co., Inc.

Before Installation

• Dimmer modules should be installed in a suitable DIN rail enclosure.
• All mains wiring should be done in accordance with local authority wiring regulations.
•  Appropriate isolation shall be maintained between Line and Low Voltage cabling.
•  For more information on network wiring, see the Leviton GreenMAX DRC Installation Guide 

and training videos at www.Leviton.com.

•  Confirm load type and amount is within product capabilities as not all load types are supported.
•  Confirm Channel/Load requirements to plan for installation, when multiple channels are to be combined 

for additional current capacity, refer to AMPlify feature for details.

1. 

Mount dimmer on DIN rail.

 

a.  Line top of module against the back of the cabinet and 

slide the module down onto rail.

 

b. Push module towards the rail.

 

c. Push up on mounting clip to lock module in place.

3.

    Wire “feeder” input to Line Input Terminal.

4.

    Connect Loads to Load Output Terminals.

5.

    Connect Network Wiring.

6.

    Power-up dimmer and confirm load operation using dimmer test 

switches. Your Dimmer is now ready for network configuration.

 

Note: Ensure last node on network is terminated.

1 Channel (10A)

NEUTRAL

LOAD   OUT 1

LOAD   OUT 2

LOAD   OUT 3

LOAD   OUT 4

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

EARTH

GND

LINE IN

TEST

TEMP

NET

AUX. IN

A      B

MODE

1

3

4

2

STATUS

Bus network cable

(CAT 6A or better)

Neutral

Line In

Channel Jumper

Channel Jumper

Channel Jumper

Load 1

10A MAX

NEUTRAL

LOAD   OUT 1

LOAD   OUT 2

LOAD   OUT 3

LOAD   OUT 4

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

EARTH

GND

LINE IN

TEST

TEMP

NET

AUX. IN

A      B

MODE

1

3

4

2

STATUS

Bus network cable

(CAT 6A or better)

Neutral

Line In

Channel Jumper

Channel Jumper

Channel Jumper

Load 1

10A MAX

NEUTRAL

LOAD   OUT 1

LOAD   OUT 2

LOAD   OUT 3

LOAD   OUT 4

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

EARTH

GND

LINE IN

TEST

TEMP

NET

AUX. IN

A      B

MODE

1

3

4

2

STATUS

Bus network cable

(CAT 6A or better)

Neutral

Line In

Load 1

5.0A MAX

Load 2

5.0A MAX

Channel Jumper

Channel Jumper

2 Channel (5A)

To remove 

from DIN rail

DIN rail

NEUTRAL

LOAD   OUT 1

LOAD   OUT 2

LOAD   OUT 3

LOAD   OUT 4

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

EARTH

GND

LINE IN

TEST

TEMP

NET

AUX. IN

A      B

MODE

1

3

4

2

STATUS

Bus network cable

(CAT 6A or better)

Load 1

2.5A MAX

Neutral

Line In

Load 2

7.5A MAX

Channel Jumper

Channel Jumper

2 Channel (1x2.5A,1x7.5A)

NEUTRAL

LOAD   OUT 1

LOAD   OUT 2

LOAD   OUT 3

LOAD   OUT 4

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

EARTH

GND

LINE IN

TEST

TEMP

NET

AUX. IN

A      B

MODE

1

3

4

2

STATUS

Bus network cable

(CAT 6A or better)

Neutral

Line In

Channel Jumper

Load 1

2.5A MAX

Load 2

2.5A MAX

Load 3

5.0A MAX

3 Channel (2x2.5A, 1x5A)

a.

c.

b.

NEUTRAL

LOAD   OUT 1

LOAD   OUT 2

LOAD   OUT 3

LOAD   OUT 4

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

EARTH

GND

LINE IN

TEST

TEMP

NET

AUX. IN

A      B

MODE

1

3

4

2

STATUS

Bus network cable

(CAT 6A or better)

Neutral

Line In

Load 1

2.5A MAX

Load 3

2.5A MAX

Load 2

2.5A MAX

Load 4

2.5A MAX

4 Channel (2.5A)

SPECIFICATIONS

Catalog No.

DRDDP-A40 (4 Channel) DRDDP-A20 (2 Channel)

Input Voltage/Frequency

120-277VAC, 50/60Hz

120-277VAC, 50/60Hz

Max Input Current

10A

5A

Load Ratings

LED,CFL, Electronic Ballast, 

Incandescent, Tungsten @ 120V

2.5A (300W)/Channel

(See channel ganging chart for additional details)

LED,CFL, Electronic Ballast, 

Incandescent, Tungsten @ 277V

2.5A (693W)/Channel

(See channel ganging chart for additional details)

IP Rating / Enclosure

IP20

Pollution Degree

2

UL Disconnection Type

Type 1Y Action, Electronic Disconnection, Non-Airgap

UL Voltage Category

6,000V

Terminal Torque Rating, 
Line & Low Voltage

0.37in-lbs (0.5Nm)

Network Connections

(2) RJ-45, CAT6A or better for connection to LumaCAN 
network. Termination provided via local termination plug.

Network Topology

•  Daisy Chain, 1600’ Max between repeaters. 
•  Home-Run topology and network length up to 10,000’  

can be achieved when using LumaCAN network repeaters  

(Leviton # NPRPT)

•  Maximum 110 nodes between repeaters 

Maximum 250 nodes on a LumaCAN network

Operating Temperature  
(In DIN rail cabinet)

0-60

o

C (32-140

o

F)

Storage Temperature

-40-70

o

C

Certifications

FCC Part 15 Class A