LumaCan™ Phase Cut Dimmer
Cat. No. DRDDP
INSTALLATION INSTRUCTION
S
ENGLISH
DI-002-DRDDP-00A-X3
WARNINGS
• TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE
AND TEST THAT POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
• To avoid electrical overload, total connected lamp load shall not exceed output rating.
• This equipment permits more than one power supply output source.
• Do not mount near gas or electric heaters.
CAUTIONS
• Use this device with copper or copper clad wire only.
• For indoor applications only.
•
Test all network cables for proper pin-out configuration prior to interconnecting devices and systems.
• If you are unsure about any part of these instructions, consult an electrician.
• Save these instructions.
Product Description
The GreenMAX™ DRC Phase Cut Dimmer provides dimming of phase control loads,
either forward or reverse phase, LumaCAN network connectivity, and full integration
into Leviton’s GreenMAX DRC system.
Installation
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!
Wiring Diagrams
2.
Remove/add channel jumpers depending on configuration.
DI-002-DRDDP-00A-X3
© 2018 Leviton Mfg. Co., Inc.
Before Installation
• Dimmer modules should be installed in a suitable DIN rail enclosure.
• All mains wiring should be done in accordance with local authority wiring regulations.
• Appropriate isolation shall be maintained between Line and Low Voltage cabling.
• For more information on network wiring, see the Leviton GreenMAX DRC Installation Guide
and training videos at www.Leviton.com.
• Confirm load type and amount is within product capabilities as not all load types are supported.
• Confirm Channel/Load requirements to plan for installation, when multiple channels are to be combined
for additional current capacity, refer to AMPlify feature for details.
1.
Mount dimmer on DIN rail.
a. Line top of module against the back of the cabinet and
slide the module down onto rail.
b. Push module towards the rail.
c. Push up on mounting clip to lock module in place.
3.
Wire “feeder” input to Line Input Terminal.
4.
Connect Loads to Load Output Terminals.
5.
Connect Network Wiring.
6.
Power-up dimmer and confirm load operation using dimmer test
switches. Your Dimmer is now ready for network configuration.
Note: Ensure last node on network is terminated.
1 Channel (10A)
NEUTRAL
LOAD OUT 1
LOAD OUT 2
LOAD OUT 3
LOAD OUT 4
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
EARTH
GND
LINE IN
TEST
TEMP
NET
AUX. IN
A B
MODE
1
3
4
2
STATUS
Bus network cable
(CAT 6A or better)
Neutral
Line In
Channel Jumper
Channel Jumper
Channel Jumper
Load 1
10A MAX
NEUTRAL
LOAD OUT 1
LOAD OUT 2
LOAD OUT 3
LOAD OUT 4
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
EARTH
GND
LINE IN
TEST
TEMP
NET
AUX. IN
A B
MODE
1
3
4
2
STATUS
Bus network cable
(CAT 6A or better)
Neutral
Line In
Channel Jumper
Channel Jumper
Channel Jumper
Load 1
10A MAX
NEUTRAL
LOAD OUT 1
LOAD OUT 2
LOAD OUT 3
LOAD OUT 4
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
EARTH
GND
LINE IN
TEST
TEMP
NET
AUX. IN
A B
MODE
1
3
4
2
STATUS
Bus network cable
(CAT 6A or better)
Neutral
Line In
Load 1
5.0A MAX
Load 2
5.0A MAX
Channel Jumper
Channel Jumper
2 Channel (5A)
To remove
from DIN rail
DIN rail
NEUTRAL
LOAD OUT 1
LOAD OUT 2
LOAD OUT 3
LOAD OUT 4
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
EARTH
GND
LINE IN
TEST
TEMP
NET
AUX. IN
A B
MODE
1
3
4
2
STATUS
Bus network cable
(CAT 6A or better)
Load 1
2.5A MAX
Neutral
Line In
Load 2
7.5A MAX
Channel Jumper
Channel Jumper
2 Channel (1x2.5A,1x7.5A)
NEUTRAL
LOAD OUT 1
LOAD OUT 2
LOAD OUT 3
LOAD OUT 4
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
EARTH
GND
LINE IN
TEST
TEMP
NET
AUX. IN
A B
MODE
1
3
4
2
STATUS
Bus network cable
(CAT 6A or better)
Neutral
Line In
Channel Jumper
Load 1
2.5A MAX
Load 2
2.5A MAX
Load 3
5.0A MAX
3 Channel (2x2.5A, 1x5A)
a.
c.
b.
NEUTRAL
LOAD OUT 1
LOAD OUT 2
LOAD OUT 3
LOAD OUT 4
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
EARTH
GND
LINE IN
TEST
TEMP
NET
AUX. IN
A B
MODE
1
3
4
2
STATUS
Bus network cable
(CAT 6A or better)
Neutral
Line In
Load 1
2.5A MAX
Load 3
2.5A MAX
Load 2
2.5A MAX
Load 4
2.5A MAX
4 Channel (2.5A)
SPECIFICATIONS
Catalog No.
DRDDP-A40 (4 Channel) DRDDP-A20 (2 Channel)
Input Voltage/Frequency
120-277VAC, 50/60Hz
120-277VAC, 50/60Hz
Max Input Current
10A
5A
Load Ratings
LED,CFL, Electronic Ballast,
Incandescent, Tungsten @ 120V
2.5A (300W)/Channel
(See channel ganging chart for additional details)
LED,CFL, Electronic Ballast,
Incandescent, Tungsten @ 277V
2.5A (693W)/Channel
(See channel ganging chart for additional details)
IP Rating / Enclosure
IP20
Pollution Degree
2
UL Disconnection Type
Type 1Y Action, Electronic Disconnection, Non-Airgap
UL Voltage Category
6,000V
Terminal Torque Rating,
Line & Low Voltage
0.37in-lbs (0.5Nm)
Network Connections
(2) RJ-45, CAT6A or better for connection to LumaCAN
network. Termination provided via local termination plug.
Network Topology
• Daisy Chain, 1600’ Max between repeaters.
• Home-Run topology and network length up to 10,000’
can be achieved when using LumaCAN network repeaters
(Leviton # NPRPT)
• Maximum 110 nodes between repeaters
Maximum 250 nodes on a LumaCAN network
Operating Temperature
(In DIN rail cabinet)
0-60
o
C (32-140
o
F)
Storage Temperature
-40-70
o
C
Certifications
FCC Part 15 Class A