background image

DI-002-DRDDP-00A-X3

© 2018 Leviton Mfg. Co., Inc.

 For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com

LIMITED 5 YEAR WARRANTY AND EXCLUSIONS

Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and 

proper use for five years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty 

excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed impro perly or in an improper environment, overloaded, misused, 

opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including 

merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a 

particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, 

lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

FOR CANADA ONLY

For warranty information and/or product returns, residents of Canada should contact Leviton in writing at 

Leviton Manufacturing of Canada Ltd to the attention of the Quality Assurance Department, 

165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9

 or by telephone at 

1 800 405-5320.

INDUSTRY CANADA COMPLIANCE STATEMENT:

This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, 

including interference that may cause undesired operation of the device. IMPORTANT! Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate 

this equipment. This Class A digital apparatus complies with Canadian CAN ICES-3(A)/NMB-3(A).

TRADEMARK DISCLAIMER: 

Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only, are/may be the trademarks of their respective 

owners; such use is not meant to imply affiliation, sponsorship, or endorsement. Patents covering this Product, if any, can be found on Leviton.com/patents.

Interface

9. 

 Indicator light - Displays device operating temperature status 

  

a.  TEMP   indicator

 

    - Green – Normal 

 

    - Amber – Warm 

 

    - Red flashing – Hot 

 

    - Red solid – Shutdown 

  

b. NET   indicator

 

    - Blinks during TX/RX of network data

10. 

 MODE LED Indicator & Button: Used to select and 

display device operating modes. (see below)

11. 

Channel status 1, 2, 3, 4: Individual indicator for each channel. 

  

a. Indicator intensity follows channel level

  

b. Alternates from 25%->50%->100%->0%

12. 

Channel button 1, 2, 3, 4: Individual channel status selector

TEST

TEMP

NET

MODE

1

3

4

2

STATUS

11

10

12

9

Configuration

Device can be programmed through the GreenMAX DRC System app when connected to a GreenMAX DRC room controller. 

In applications where you are not using GreenMAX DRC room controllers, limited configuration capability is available from the front panel of the devices.

1.

 

 To enter program mode: 

Press and hold for 

approximately 5 seconds  

until indicator turns red.

2. 

 To toggle between  

Phase Control and AMPlify setup, 

press and release.

   

Red - Phase Control 

   

Blue - AMPlify

TEST

TEMP

NET

MODE

1

3

4

2

STATUS

To toggle between Forward and Reverse Phase 

Control, press and release the corresponding 

channel button.
  ON - Forward Phase Control 

  OFF - Reverse Phase Control

Phase Control Method Selection

TEST

TEMP

NET

MODE

1

3

4

2

STATUS

AMPlify Feature Mode Selection

Only a limited number of configurations are supported from the front 
panel. Other configurations can be set from the GreenMAX DRC 
system programming tools.

Channel LED indicators lights up to indicate that the channel is grouped 

together. Press/Release the channel buttons to change the grouping.

Refer to chart below to see which LED Indicator combinations 

correspond with each channel mode.

FCC COMPLIANCE STATEMENT:

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference 

when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause 

harmful interference to radio communications.  Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. 

Any changes or modifications not expressly approved by Leviton could void the user’s authority to operate this equipment.

1. 

 Line In and Neutral: Common to all channels.

2. 

Load Out 1, 2, 3, 4: Connects to the load for each channel.

3. 

Neutral: Individual neutral for each channel.

4. 

Earth Ground: Common to all channels

5. 

LumaCan Address & Start Channel Assignment DIP Switches

6. 

Aux In A & B: Auxiliary active high (+24V) or dry contact input (for future use)

7. 

DIN Rail Mounting Clip

8. 

LumaCan: Network input and feedthrough RJ45

NEUTRAL

LOAD   OUT 1

LOAD   OUT 2

LOAD   OUT 3

LOAD   OUT 4

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

EARTH

GND

LINE IN

TEST

TEMP

NET

AUX. IN

A      B

MODE

1

3

4

2

STATUS

Bus network cable

(CAT 6A or better)

3

8

6

5

7

2

2

1

1

4

2

2

3

3

3

LumaCAN Network Termination

LumaCAN Network Addressing

The last Node in a LumaCAN network must have the termination jumper/plug installed.Your unit ships with a termination plug 

(P/N #LCTRM) installed into one of the RJ-45’s.

Set DIP switches 1-8 to the desired LumaCAN address.

A unique LumaCAN address ID must be set for each LumaCAN device. Valid node addresses are 1-250. If the node ID’s are 

defined in your Contract Document, set to that address.

If not, ensure that the ID is unique for each device in the system. It’s helpful, although not required, that the location of each node 

ID is documented for use by Leviton Field service during system commissioning.

To set the node ID, set the DIP switches to the desired ID following the process below. Several examples are provided.

a.   If this device is at the end of the line, the jumper shall remain installed and the network cable shall be connected to the other 

plug.

b.   If this device will be in the middle of a network run, remove the plug and save for future use.
c.   If the plug was removed but is at the end of the line, the termination plug must be reinstalled.

1

2

3

4

5

6

7

8

ON

1

2

4

8

16

32

64

128

Switch Values

ID Address Value = Sum of Switch Values

ID 86 = 2+4+16+64

1

2

3

4

5

6

7

8

ON

ID 2

ID 1

1

2

3

4

5

6

7

8

ON

ID 3

1

2

3

4

5

6

7

8

ON

ID 4

1

2

3

4

5

6

7

8

ON

ID 5

1

2

3

4

5

6

7

8

ON

ID 6

1

2

3

4

5

6

7

8

ON

ID 38

1

2

3

4

5

6

7

8

ON

ID 86

FCC SUPPLIERS DECLARATION OF CONFORMITY:

Model DRDDP – LumaCAN Phase Cut Dimmer 

Manufactured by: Leviton Manufacturing Inc. 201 N Service Rd, Melville, NY 11747

Phone: 800.323.8920

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, 

including interference that may cause undesired operation.

To perform a factory reset: Press and hold for approximately 

20 seconds until indicator light flashes rapidly, then release.   

The device will then revert to the factory default operation.  

NOTE: Default operation is single channel mode.

AMPlify Feature

Two or more channels can be wired in parallel to AMPlify your load carrying 

capacity.
In order to use this feature:

•  Jumper must be installed between channels you want to combine.
•  Software must be configured. Go to Leviton.com.

 The chart to the right indicates the configurations and operating modes which 

are supported:

Mode

No. of

Channels

Channel 1 

Capacity

Channel 2 

Capacity

Channel 3 

Capacity

Channel 4 

Capacity

LED Indicators

1

2

3

4

1*

1

10A

Jumper to 1

Jumper to 2

Jumper to 3

ON

ON

ON

ON

2A

2

2.5A

7.5A

Jumper to 2

Jumper to 3

OFF

ON

ON

ON

3

3

2.5A

2.5A

5A

Jumper to 3

OFF OFF

ON

ON

4

4

2.5A

2.5A

2.5A

2.5A

OFF OFF OFF OFF

The following mode is only configurable via GreenMAX DRC App

2B

2

5A

Jumper to 1

5A

Jumper to 3

*  Default Mode from the factory is single (1) channel mode with jumpers installed between all four 

channels. In this mode, the dimmer operates like a single channel dimmer with max capacity of 10A. 

For other configuration, jumpers must be removed as per the chart above.