Hold Down

 

Programming Of Presets 

 

DLE1210 Installation Manual Rev G.docx   

7

 

 
AUX Input 

- This is a dry contact interface that is active low.  The dry contact is connected between the AUX 

and GND terminals on the DyNet connector strip.  The function of  the AUX input is programmable.  Ensure 
that the cable length between the dry contact and terminal strip is no longer than 2 metres.

 

 
Service LED

 - The Service LED has 3 signalling modes, which are useful for troubleshooting:

 

Blinking slowly (1Hz) = Normal Operation 
Blinking fast (0.25Hz) = Network Activity Detected 
On = Fault 
 

Service Switch

 - The Service Switch has three functions: 

1 push = Transmit Network ID 
3 pushes = All Channels 100% 
Push & hold for 4 sec = Reboot 

 

TOP  SET

  - This  adjusts  the  maximum  output  that  all  other  control  sources  can  select,  ie: if  the  Top  Set  is 

fully clockwise, 100% selected by a control source  will give 100%  output.   If it is fully  anti-clockwise, 100% 
selected by a control source will give 50% output.  This control is useful for extending lamp life and can be 
operated  without  any  form  of  network  control,  effectively  turning  the  device  into  a  stand-alone  power 
conditioner and lamp protector. 

 

 

 

dimmable lamps chart 

 

INCANDESCENT 
LAMPS 

Incandescent  lamps  are  easily  dimmed  using  all  Dynalite  controllers.    The  soft  start  and 
voltage  limit  features  will  extend  lamp  life.    Lamp  life  can  be  further  extended  using  the 
voltage limit adjustment.  

TUNGSTEN 
HALOGEN 
LAMPS 

Tungsten  halogen  and  other  transformer  loads  are  easily  dimmed  using  all  Dynalite 
controllers.    The  soft  start,  cleanup  and  surge  limiting  features  will  protect  lamps  against 
premature failure.  Lamp life can be extended using the voltage limit adjustment.  

FLUORESCENT 
LAMPS (38mm) 

38mm rapid start lamps can be successfully dimmed to 40% using an inexpensive filament 
driver  transformer.    For  better  performance,  an  electronic  HF  dimming  transformer  is 
recommended.    The  power  factor  capacitors  need  to  be  wired  to  the  supply  side  of  the 
dimmer.    Some  Dynalite  controllers  include  a  supplementary  relay  contact  for  control  of 
power factor capacitors.  If electronic ballasts are not used, cabling and controllers should 
be de-rated by approx. 60% to allow for reactive current.  Contact your Dynalite dealer for 
more information. 

FLUORESCENT 
LAMPS (26mm) 

26mm  slimline  tubes  can  be  dimmed  to  as  low  as  5%  using  a  dimmable  full  electronic 
ballast  or  electronic  dimming  transformer.    No  de-rating  is  necessary  with  electronic 
ballasts.  Contact your Dynalite dealer for more information. 

COMPACT 
FLUORESCENTS 

Only some types of 4 pin PL lamps can be successfully dimmed using dimmable electronic 
ballasts.  Best results are achieved with DC controlled HF ballasts 

NEON 

Only argon filled neon lamps can be reliably dimmed.  The power factor capacitors need to 
be  wired  to  the  supply  side of  the  dimmer.    Cabling  and  controllers  should  be  de-rated  by 
approx.  60%  to  allow  for  reactive  current.    Any  open  circuit  monitoring  on  the  neon 
transformer must be suitable for dimming.  

HID SOURCES 

Mercury  vapour  and  sodium  lamps  can  be  dimmed  to  approx.  45%.    For  successful 
dimming to low levels, the fade time should be set to very slow speeds (> 30sec) to avoid 
"cut out" problems.  The power factor capacitors need to be wired to the supply side of each 
dimmer.    Some  Dynalite  controllers  include  a  supplementary  relay  contact  for  control  of 
power  factor  capacitors.    Cabling  and  controllers  should  be  de-rated  by  approx.  60%  to 
allow for reactive current.  Contact your Dynalite dealer for more information. 

METAL HALIDE 

Metal halide lamps give similar dimming performance to other HID sources.  However, the 
colour  of  the  light  tends  to  change  in  an  unpredictable  way  in  most  lamps  when  dimmed 
(often permanently).  Most lamp manufacturers do not recommend dimming of metal halide 
lamps.  Contact your Dynalite dealer for more information. 

Содержание Dynalite DLE1210

Страница 1: ...8 9333 dynalite info philips com Philips com dynalite DLE1210 12 x 10A Leading Edge Dimmer Installation Manual contents Warning 2 Dimmable Lamps Chart 7 Features 2 Troubleshooting 8 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Hardware Controls 7 ...

Страница 2: ... switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Do not operate as a single phase device Output Circuits The load on a circuit should not exceed the speci...

Страница 3: ...internal view DLE1210 Installation Manual Rev G docx 3 For spare parts please call your nearest Dynalite Customer Service Centre and specify DLE1210 ...

Страница 4: ...E1210 has integral mounting brackets attached to the enclosure The brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DLE1210 can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling o...

Страница 5: ... is below the maximum capacity of an individual channel which is 10A Do not use a common neutral at a remote location Emergency Lighting Connections Connect emergency lighting circuit active to the load side on the circuit breaker for the relevant channel as indicated by the labels next to the circuit breakers Do not remove any cables that may already be terminated at this location Energising the ...

Страница 6: ...r GND one pair paralleled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair Paralleled for GND Orange White pair Paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The rec...

Страница 7: ...r better performance an electronic HF dimming transformer is recommended The power factor capacitors need to be wired to the supply side of the dimmer Some Dynalite controllers include a supplementary relay contact for control of power factor capacitors If electronic ballasts are not used cabling and controllers should be de rated by approx 60 to allow for reactive current Contact your Dynalite de...

Страница 8: ...r losses Check that the breaker terminals are tight Fluorescent lights won t dim Wrong type of ballast or ballast incorrectly wired Check ballast type Check actual wiring against ballast manufacturer s diagram specification Supply 230V 14 50 60Hz 3 Phase Y 40A per phase Outputs 12 x leading edge dimmed outputs at 10A per channel Protection 10A 6KA thermal magnetic breaker on each channel Regulatin...

Отзывы: