background image

275AP-SB13-01 

 

            

Figure 3: 275AP/APF/AF Valve with Steel Chamber 

27.88 [708.0]

15.88 [403.2]

7.88 [200.0]

8.25 [209.6]

Ø6.63 [168.3]

4.50 [114.2]

3/4" FPT

1/2" FPT

LEVEL EYE 

®

3/4" FPT

 

 

Figure 4: 

Optional Mounting Flange 

(6) 7/16-20 NF

0.63 [15.9]

Ø2.91 x .34DP

SOCKET

Ø3.75 [Ø95.3]

BC

Ø4.50 [114.3]

 

 
Figure 5: 275AP/APF Piloting 700H Valve 

 

 

Figure  6:  275AF  Maintaining  Oil  Levels  in  Multiple 
Compressor Crankcases 

 

 
 

 
The 275AF valves may be used to maintain the oil level in one 
or more compressor crankcases (Figure 6). Note that if the oil 
reservoir level is less than 2 feet above the crankcase level, it 
should  be  pressurized  5  to  20  psi  (0.3  to  1.4  bar)  higher  than 
the crankcase.  

 
 
REPLACEMENT PARTS  

 

Basic replacement parts are illustrated in Figure 7 and listed in 
Table 1. 
 
When  contacting  Phillips  for  replacement  parts,  have  the 
complete  valve  model  and  serial  number  (shown  on  the  valve 
nameplate)  available  to  ensure  you  receive  the  correct 
components. For example: “275APF-BZA” is a complete valve 
model,  and  “990123”  or  “E-12345”  are  complete  serial 
numbers. 

 

 
SERVICE INSTRUCTIONS 

 
Lever  pin  /  float  block  removal  and  replacement: 

If  it  is 

necessary to remove the lever pin (411) and float block (230Z) 
during servicing, first cut one end of the pin flush with the valve 
body. Then either pull the pin out with pliers, or carefully drive it 
out  with  a  punch.  Retain  the  spacers  (11S)  for  re-assembly. 
After  re-assembly,  peen  the  lever  pin  to  retain  in  place  and 
check for free movement of valve components. 
 

Needle and seat replacement: 

The needle and seat bushing 

are lapped in the factory to create a matched set. If either the 
needle  or  seat  bushing  show  signs  of  wear  or  damage,  both 
parts  must  be  replaced.  To  inspect  or  replace  the  needle  and 
seat perform the following steps.  
 
1.  Remove the lever pin and float block as described above.  
2.  Remove the old seat bushing and install a new one using 
PTFE tape or other pipe sealant on the threads. 
3.  Remove the old needle from the adjusting nut (204E), lock 
washer  (55),  and  lock  nut  (224).  Reassemble  the  nut  and 
washer loosely on the new needle. 
4.  Insert  the  new  needle  into  the  new  bushing.  Install  the 
float  block  /  float  assembly  (without  spacers)  loosely  in  the 
valve body with the lever pin. 

DO NOT

 

PEEN THE LEVER PIN 

AT THIS TIME.

 

 
(Continued on next page) 
 

TO LOWER 
PRESSURE 

VESSEL 

18 in.  

MIN. 

CONDENSER 
DRAIN 

UPPER EQ LINE 

LOWER EQ LINE 
(DO NOT TRAP 
ON NH3) 

MANUAL BYPASS 

PILOT LINE 
1/4” NOMINAL IPS 

700H SERIES 
PILOT 
OPERATED 
VALVE WITH 
CLOSE-COUPLED 
STRAINER 

275AP/APF PILOT 
FLOAT VALVE 

UNION 

OIL RECEIVER / STILL: 
AT LEAST 2 FT HIGHER 
ELEVATION THAN CRANK 
CASE FOR GRAVITY FEED; 
CAN BE AT SAME ELEVATION 
AS CRANKCASE IF AT HIGHER 
PRESSURE. 

275AF: CHAMBER 
EQUALIZED TO 
CRANKCASE 

275AF: CHAMBER 
EQUALIZED TO 
CRANKCASE 

2 FT. 

Содержание 275AP series

Страница 1: ...F AP APF valves are available without a chamber Figure 1 with a cast iron chamber Figure 2 or with a welded steel chamber Figure 3 An optional mounting flange is available for mounting the valve without a chamber Figure 4 The valve should always be oriented such that the 1 2 FPT connection is toward the top of the valve and the front face is vertical This will ensure that the float moves appropria...

Страница 2: ...e pin out with pliers or carefully drive it out with a punch Retain the spacers 11S for re assembly After re assembly peen the lever pin to retain in place and check for free movement of valve components Needle and seat replacement The needle and seat bushing are lapped in the factory to create a matched set If either the needle or seat bushing show signs of wear or damage both parts must be repla...

Страница 3: ...nto the adjusting nut so the float is slightly above horizontal when the needle is seated in the bushing Figure 8 Tighten the lock nut to secure needle position 7 Remove the lever pin and pull the needle from the bushing Reassemble the float block to the valve body using the lever pin and spacers 11S to ensure the float block 230Z is centered on the link 431 8 Peen the lever pin to retain in place...

Страница 4: ...The pressure above the 700H piston drops and the piston rises due to pressure underneath opening the valve port and allowing flow Conversely as the liquid level drops the 275AP opens and pressure above the piston rises closing the 700H port with spring assist Match the condenser condition liquid high or low with pressure gauge reading condensing or downstream pressure and note the possible causes ...