![Philip Payne Specto-XT Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/philip-payne/specto-xt/specto-xt_manual_1538024004.webp)
21LFT32418 Issue 3
PN 2644C Apr 20
G B - N O T I C E T O C O N T R A C T O R - P L E A S E P A S S T H I S L E A F L E T T O T H E E N D - U S E R .
F R - A L’AT T E N T I O N D E L’ I N S TA L L AT E U R - M E R C I D E T R A N S M E T T R E C E D O C U M E N T À L’ U T I L I S AT E U R .
D E - H I N W E I S A N D I E M O N T A G E F I R M A - B I T T E G E B E N S I E D I E S E I N F O R M A T I O N A N I H R E N K U N D E N W E I T E R .
I T - AV V I S O P E R C O N T R A C T O R - L A P R E G H I A M O D I I N F O R M A R E I L LU S T R AT I V O A L L E U T E N T E F I N A L E .
S E - I N F O R M A T I O N T I L L E N T R E P R E N Ö R E N – V Ä N L I G E N V I D A R E B E F O R D R A D E T T A I N F O R M A T I O N S H Ä F T E T I L L S L U T A N V Ä N D A R E N .
E S - N O T A A L C O N T R A T I S T A – P O R F A V O R H A G A L L E G A R E S T E F O L L E T O A L C L I E N T E F I N A L .
N L - M E D E D E L I N G V O O R D E A A N N E M E R : G E E F D E Z E I N F O R M A T I E D O O R A A N D E E I N D G E B R U I K E R .
N 0 - N O T A T T I L E L E K T R I K E R – V Æ R V E N N L I G Å G I D E T T E S K R I V T I L S L U T T B R U K E R .
P L - I N F O R M A C J A D L A M O N T A Ż Y S T Y – P R O S Z Ę P R Z E K A Z A Ć I N S T R U K C J Ę M O N T A Ż O W Ą D L A O D B I O R C Y .
4
THORNHILL ROAD, LODE LANE,
SOLIHULL, B91 2HB, ENGLAND.
e-mail:
Web:
www.philippayne.co.uk
☎
+44 (0)121 705 2384
A SUBSIDIARY OF F.W. THORPE PLC
ISO 9001 FM55077
TO READ EMERGENCY STATUS
TO READ EMERGENCY FAULT STATUS
FUNCTION
BUTTON
DISPLAY
FUNCTION
BUTTON
DISPLAY
1
Switch on the Programmer
IRPR Version 1.90
1
Switch on the Programmer
IRPR Version 1.90
2
Scroll to the
<Emergency Status>
<Emergency Status> menu
2
Scroll to the
<Emergency Status>
<Emergency Status> menu
3
Select the menu
<Emergency Status>
Start function test
3
Select the menu
<Emergency Status>
Start function test
4
Scroll to Read test status
Read test status
4
Scroll to Read test status
Read test status
5
Press Read
Read test status
5
Press Read
Read test status
10
Battery duration test failure y/n
BateryDuraFail: n*
10
Function test complete y/n
FunctiTestDone: y*
11
Battery failure y/n
BatteryFailure: n*
11
Duration test complete y/n
DuratiTestDone: y*
12
Emergency lamp failure y/n
EmergeLampFail: n
12
Battery charged y/n
BatteryCharged: y*
15
Function test failed y/n
FunctiTestFail: n*
16
Duration test failed y/n
DuratiTestFail: n*
9
Circuit failure y/n
CircuitFailure: n*
9
Autotest inhibit y/n
InhibitMode: n*
6
Scroll to
Failure Status
Failure Status
0 0 0 0 0 0 0 0
6
Scroll to
Emergency Status
Emergency Status
0 0 0 0 0 0
13
Function test maximum
FuncTestExceed: n*
delay exceeded y/n
13
Function test pending y/n
FuncTestPendin: y*
14
Duration test maximum
DuraTestExceed: n*
delay exceeded y/n
14
Duration test pending y/n
DuraTestPending: y*
7
Press select to
Failure Status*
define status
0 0 0 0 0 0 0 0
7
Press select to
Emergency Status*
define status
0 0 0 0 0 0
8
Scroll through to see
Failure Status*
fault status
0 0 0 0 0 0 0 0
8
Scroll through to see
Emergency Status*
emergency status
0 0 0 0 0 0 0 0
Philip Payne products should not be modified. Any
modification may render the product unsafe and will
invalidate any Safety/Approval marks.
MODIFICATIONS
MAINTENANCE
The Programmer should not be subjected to undue
mechanical shock or extremes of temperature. Clean only
with a clean dry cloth.
✘
✔
Only one Specto-XT device in view of the programmer.
The Programmer should
only communicate with
one luminaire at a time.
If luminaires are close
together use the supplied
IR tube to ensure correct
operation.
When programming at height the
programmer has a built in laser to
assist with alignment.