Specto-XT Controls
Specto-XT Programmer
INTRODUCTION TO THE
SPECTO-XT SYSTEM
The Specto-XT system provides a simple,
effective means of controlling luminaires
independently or in groups (zones).
SPECTO-XT LUMINAIRES
The
Specto-XT Programmer
allows alteration
of the factory set values to tailor the
installation to the users requirements.
Specto-XT compatible emergency luminaires
can be programmed, tested and diagnosed
with the Specto-XT Programmer.
IP43
IP22
IP40
IP20
IP23
IP44
IP50
IP53
IP54
IP54
IP55
IP60
IP65
IP66
IP67
IP68
III
IP40
D
IK10
IP42
IP64
IP30
THE SPECTO-XT PROGRAMMER
The
Specto-XT Programmer
has six ‘touch pad’ buttons.
DISPLAY
On the first LCD line the menu point is displayed. On
the second line, the status line, the possible settings for
this menu point are shown. During a data transmission,
the actual transmission status (as well as any error
messages) is shown.
TECHNICAL DATA
■
Dimensions : 198 x 121 x 52mm
■
Power : 4-off AA/1.5V Battery
(supplied)
GB - CLASS II LASER. DO NOT STARE INTO BEAM
FR - LASER DE CLASSE 2. NE PAS REGARDER LE FAISCEAU
DE - LASERKLASSE II. BITTE NICHT IN DEN STRAHL BLICKEN
SE - KLASS 2 LASER. TITTA INTE IN I LASERSTRÅLEN
ES - LASER CLASE II. NO MIRE FIJAMENTE AL RAYO
NL - KLASSE 2 LASER PRODUCT. STAAR NIET IN DE STRAAL
NO - KLASSE II LASER. STIRR IKKE INN I LYSKILDEN
PL - LASER KLASY II. NIE PATRZEC PROSTO W PROMIEN
GROUP
ONE
GROUP
ONE
GROUP
TWO
GROUP
TWO
GROUP
THREE
GROUP
THREE
GR
OUP SIX
GR
OUP
SIX
GROUP
FOUR
GROUP
FOUR
GROUP
FIVE
GROUP
FIVE
= Group
= Building
= Device
Building 1
Building 2
1
2
3
4
5
1
2
3
4
5
BUILDING, GROUP & DEVICE ADDRESS - Example
All luminaires within groups 1-6 have their building address set to 1,
and their relevant group address set. This will ensure that all lights in
Building 1, and only Building 1, communicate within their group, but
groups do not communicate with each other. The device address is
used to identify individual luminaires on the system.
BUILDING 1
BUILDING 2
By setting the building address to 2, these luminaires will not
communicate with the adjacent building. All luminaires within a group
will communicate, but groups will remain separate.
ESSENTIAL CONFIGURATION
Each Specto-XT device requires programming with three addresses. Programming is carried out using the Programmer. In order to prevent areas of
a building inadvertently communicating it is essential that addresses are correctly set and we recommend they are recorded for future reference.
Identifies devices that are within the
same system and forms the boundary
for the wireless mesh to prevent
adjacent buildings communicating.
The building address can be set
between 1-254.
The control group, all luminaires with
the same building address and the same
group address will work together. Up to
254 different groups can be created in
one building.
The group address can be set between
1-254.
The unique device address within each
group. This is used to identify individual
luminaires within a group.
The device address can be set between
1-254.
Enable RF communications.
BUILDING ADDRESS
GROUP ADDRESS
DEVICE ADDRESS
1. ESSENTIAL
2. ESSENTIAL
3. ESSENTIAL
4. ESSENTIAL