background image

16 | 

Page

 

V2.0 

 

 

Table 16 

– Field Wiring Tools

 

Model 

Line Side 

Load Side 

 

Model 

Line Side 

Load Side 

PT007 

3/16" Hex 

3/16" Hex 

 

PT407 

3/16" Hex 

3/16" Hex 

 

PT410 

PT010 

 

PT415 

PT020 

 

PT420 

PT030 

5/16" Hex 

 

PT430 

PT040 

 

PT440 

PT050 

3/8" Hex 

5/16" Hex 

 

PT450 

PT060 

 

PT460 

5/16" Hex 

PT075 

 

PT475 

 

 

 

 

PT4100 

 

 

 

 

 

 

 

Model 

Line Side 

Load Side 

 

Model 

Line Side 

Load Side 

PTE007 

Phillips 

Screwdriver 

Flathead 

Screwdriver 

 

PTE407 

Phillips 

Screwdriver 

Flathead 

Screwdriver 

PTE007QT 

 

PTE407QT 

PTE010 

 

PTE410 

PTE010QT 

 

PTE410QT 

PTE015 

3/16" Hex 

 

PTE415QT 

PTE020 

 

PTE420QT 

 
 

Table 17 

– 

Optional Circuit Breaker Wire Size and Torque 

Models 

Circuit Breaker 

Family 

Min 

Max 

Min Torque 

(in-lb) 

Wire 

Strip 

PT007 
PT010 
PT407 
PT410 
PT415 
PT420 
PT430 

LS UTE100 

14 

10 

31.9 

0.7” 

39.9 

47.8 

55.7 

PT020 
PT440 

LS UTS150 

14 

36.2 

1.01” 

12 

10 

47.8 

2/0 

133.6 

PT030 
PT450 
PT460 
PT475 

LS UTS250 

1/0 

2/0 

254.9 

1.27” 

3/0 

4/0 

350.5 

250 

kcmil 

300 

kcmil 

350.5 

PT040 
PT050 

PT4100 

LS UTS400 

1/0 

300 

kcmil 

358.4 

1.76” 

350 

kcmil 

600 

kcmil 

477.9 

 

Содержание HPASEPERFECT PT007

Страница 1: ...Digital Phase Converter Operation Installation Manual Single Phase to Three Phase Solid State Technology 98 7 Efficient 240V 480V...

Страница 2: ...No portion of this publication or its contents may be duplicated by any means electronic or otherwise without the express written consent of Phase Technologies LLC V2 0_04072021 Digital Phase Convert...

Страница 3: ...phase voltage balance and operates at 98 7 efficiency Output voltage is sinusoidal with low harmonic content making it safe to operate sensitive electronic equipment The Phase Perfect was designed to...

Страница 4: ...ze the equipment before servicing WARNING Risk of electric shock De energize the unit by disconnecting all incoming sources of power then wait 30 minutes for internal charges to dissipate before servi...

Страница 5: ...the terminal blocks shall be secured by tightening the terminal screws to a torque value listed in Table 12 Table 15 CAUTION The input wire gauge must be sized for the single phase input current whic...

Страница 6: ...RANCH CIRCUIT PROTECTION 11 GROUNDING 12 WIRE SIZING 14 CONNECTING THE LOAD 14 CONNECTING TO FIELD WIRING TERMINALS 17 ROUTING POWER CABLES 19 ON OFF CONTROL WIRING 20 OPERATION 22 LCD STATUS SCREEN 2...

Страница 7: ...r from the DC bus to generate the third leg of the three phase output The third leg is generated to limit voltage imbalance between the three legs to 2 Voltage imbalance is calculated according to the...

Страница 8: ...2 Page V2 0 MODELS AND RATINGS Figure 2 Phase Perfect Nomenclature Figure 3 Phase Perfect Enterprise Nomenclature...

Страница 9: ...dBA Audible Noise PTE QT Models 75 dBA Start Delay on Power Up 2 sec Electrical Specifications Table 2 240 V PT Models and Ratings Model Power HP Output kVA Max Steady State Output Current AAC Input V...

Страница 10: ...BTU hr Preliminary Full Load Energy Loss Typical BTU hr PT407 7 5 10 8 13 440 520 22 52 177 479 PT410 10 14 9 18 32 68 232 661 PT415 15 22 4 27 47 71 242 994 PT420 20 26 6 32 55 74 252 1180 PT430 30...

Страница 11: ...16 Weight lbs 51 60 51 65 71 72 Table 8 480V PT Models Enclosure Specifications Models PT407 PT410 PT415 PT420 PT430 PT440 PT450 PT460 PT475 PT4100 Indoor NEMA 1 HxWxD 31 3 8 x 17 3 16 x 15 1 16 36 15...

Страница 12: ...6 Page V2 0 Dimensional Drawings Figure 4 PT Small Frame Dimensions...

Страница 13: ...7 Page V2 0 Figure 5 PT Medium Frame Dimensions...

Страница 14: ...8 Page V2 0 Figure 6 PT Large Frame Dimensions...

Страница 15: ...9 Page V2 0 Figure 7 PTE Frame 1...

Страница 16: ...10 Page V2 0 Figure 8 PTE Frame 2...

Страница 17: ...he unit must be maintained Allow six inches on each side and top and at least 18 inches below Ensure air intake and exhaust openings are not obstructed If the unit is mounted in a small room cabinet o...

Страница 18: ...rigid stranded copper wire Table 10 Ground Wire Specifications Models Recommended Circuit Breaker A Wire Range AWG Min Max PT007 PTE007 60 10 2 PT010 PTE010 80 8 2 PTE015 125 6 2 PT020 PTE020 150 6 2...

Страница 19: ...tion factor Input Wiring Recommendations Min Wire Gauge 60 C Min Wire Gauge 75 C PT007 PTE007 4 AWG 6 AWG PT010 PTE010 3 AWG 4 AWG PTE015 1 0 AWG 1 AWG PT020 PTE020 1 0 AWG PT030 300 kcmil 4 0 AWG PT0...

Страница 20: ...connect single phase loads to the manufactured leg T3 This places unnecessary load on the phase converter and may violate electrical code in some areas Apply overload and short circuit protection to...

Страница 21: ...E407 PTE407QT PTE410 PTE410QT PTE415QT PTE420QT PTE015 PTE020 Wire Size Torque Wire Size Torque 2 20 AWG 17 5 in lb 2 0 6 AWG 8 AWG 10 14 AWG 120 in lb 40 in lb 35 in lb Table 14 Output Power Terminal...

Страница 22: ...7 Phillips Screwdriver Flathead Screwdriver PTE007QT PTE407QT PTE010 PTE410 PTE010QT PTE410QT PTE015 3 16 Hex PTE415QT PTE020 PTE420QT Table 17 Optional Circuit Breaker Wire Size and Torque Models Cir...

Страница 23: ...ld Wiring Terminals Figure 12 PT Large Frame Field Wiring Terminals Table 18 Power Terminal Descriptions Terminal Name Description L1 L2 Single phase input power terminals T1 T2 T3 3 Phase output powe...

Страница 24: ...18 Page V2 0 Figure 13 PTE Field Wiring Terminals All models except PTE015 and PTE020 Figure 14 PTE Field Wiring Terminals PTE015 and PTE020...

Страница 25: ...gure 15 Figure 19 Route power cables through the supplied openings in the bottom of the enclosure using appropriate conduit or strain relief devices Important Note If new openings are cut be sure to c...

Страница 26: ...ry installed jumper wire and replace with a switch Jumper wire can be seen in Figure 20 below Figure 20 Control Terminal Locations When AUX1 to COM or AUX2 to COM is closed the output is energized aft...

Страница 27: ...h setting Table 19 Control Terminal Ratings and Descriptions Terminal Description Rating Comments AUX1 Auxiliary Input 1 Dry contact type Pullup Voltage 5 volts galvanically isolated Digital input Com...

Страница 28: ...t cover with the switch in the ON position exposes the user to the risk of electric shock WARNING Risk of electric shock Disconnect all incoming sources of power and wait 30 minutes before opening the...

Страница 29: ...adjusting the voltage of the generated leg In this mode the output voltage may not be balanced This function is typically used to prevent overheating of the VFD due to unbalanced currents induced by t...

Страница 30: ...ing should only be used if elevator is tripping due to a drop in input voltage To enable Elevator Mode follow the steps below Step Directions Display Reading After Step 1 Turn power to PT OFF 2 Remove...

Страница 31: ...usting output voltage make changes in small increments to begin then let the menu time out to save the change After Programmed Successfully is shown on the display return switches to the OFF position...

Страница 32: ...sensor on the heat sink has failed or its cable is disconnected Manual UNBALANCE BUS VOL Potential damage to a bus capacitor or degradation of the bus balancing resistor Auto VOLTAGE UNBALANCE Output...

Страница 33: ...operating parameters UNIT WILL OPERATE WHILE IN THIS MODE ON OFF LCD screen will show Master Fault Log non resettable count of all faults UNIT WILL NOT OPERATE WHILE IN THIS MODE ON ON LCD screen wil...

Страница 34: ...ernal to the unit AUX1 and AUX2 open Check the jumper or switches connected to the AUX1 and or AUX2 inputs Signals to the Control Terminals corrupted Shielded cable is required for AUX terminal leads...

Страница 35: ...nspected and cleaned annually or more frequently if located in a hot or dirty environment Special attention should be given to the following Power terminals Periodically inspect for loose connections...

Страница 36: ...capacitance of either is below the 50 Capacitance value in Table 24 contact Phase Technologies for replacement For PT Medium and Large Frames disconnect wires from L2 and use a multi meter to measure...

Страница 37: ...407 PTE407QT PTE410 PTE410QT PTE415QT PTE420QT 4 20 uF 10 uF PT030 PT040 PT440 PT450 PT460 PT475 8 40 uF 20 uF PT050 PT060 PT075 PT4100 8 80 uF 40 uF For 240V PTE models PTE0XX disconnect wires from J...

Страница 38: ...chnologies for replacement Be sure to reconnect wires to JL2 before powering unit on again Figure 32 Measuring PTE4XX Filter Capacitors Fuses There are several replaceable fuses in the converter Each...

Страница 39: ...screws fastening the baffle to the side of the heatsink The heat sink baffle is necessary for proper cooling and must be replaced before resuming operation If not properly replaced warranty may be voi...

Страница 40: ...ad characteristic with a proprietary algorithm that limits inrush current on the manufactured leg during startup to prevent nuisance tripping During startup voltage is folded back when current exceeds...

Страница 41: ...tart motor loads 1 0 10 0 100 0 1000 0 10000 0 0 50 100 150 200 Time sec Current A Overcurrent Motor Starting Sourcing Limit PT407 PT410 PT415 PT420 PT430 1 0 10 0 100 0 1000 0 10000 0 100 200 300 400...

Страница 42: ...e converters 50 HP and larger should not be used to cross the line start motor loads 1 0 10 0 100 0 1000 0 10000 0 0 100 200 300 400 500 600 Time sec Current A Overcurrent Sourcing Limit PT440 PT450 P...

Страница 43: ...thorized Service Center is the responsibility of the purchaser Return transportation is provided by Phase Technologies 2 Installations must comply with all national and local electrical codes Exclusio...

Страница 44: ...w w w p h a s e t e c h n o l o g i e s c o m 222 Disk Drive Rapid City SD 57701 866 250 7934 Toll Free 605 343 7934 Main...

Отзывы: