51 |
P a g e
6.6
Start-Up and Shut-Down Ramp Times
Start-up and shut-down ramp times specify the time required to go from
MIN FREQUENCY
to
MAX
FREQUENCY
or vice versa. Ramp times and profiles are adjustable using keypad navigation.
The factory default setting for START UP RAMP
is 10 seconds and 4 seconds for
SHUTDOWN
RAMP.
Factory settings activate the
COAST TO STOP
parameter to reduce nuisance tripping from
high inertia loads. Coast to stop inactivates the
SHUTDOWN RAMP
parameter.
Submersible Pump Parameter and Minimum Frequency
Most submersible pump motor manufacturers require the motor to reach 30 Hz within one second in
order to protect the pump from damage. Because the SD & 2XD Series drives are frequently used for
pumping applications, it has a parameter,
SUBMERSIBLE PUMP
that limits the time the motor runs
below 30 Hz to one second.
When
SUBMERSIBLE PUMP
is set to YES, the motor speed will ramp to minimum frequency in one
second, then ramp to the maximum frequency in a total of 10 seconds. The ramp times can be
changed through the adjustable parameter,
START UP RAMP
.
The factory default setting for
SUBMERSIBLE PUMP is YES and MIN FREQUENCY is 30 Hz.
When the
SUBMERSIBLE PUMP
parameter is set to YES, the motor will ramp from stop to the
maximum frequency in 10 seconds in a linear fashion as depicted in
Figure 29
– Default Start-Up Ramp (SUBMERSIBLE PUMP parameter enabled)
To
set
the
minimum
frequency,
navigate
to
the
keypad
Main
Menu
item:
CHANGE PARAMETER VALUES > CHANGE OPERATING PARAMETERS > MIN FREQUENCY >
30 Hz.
When
SUBMERSIBLE PUMP
is set to NO ramp times will be linear, as depicted in
Содержание 2XD Series
Страница 10: ...4 P a g e 2 3 Dimensional Drawings Figure 5 SD Series Line Drawing...
Страница 11: ...5 P a g e Figure 6 SD Series Line Drawing if selected with optional breaker see Figure 9...
Страница 12: ...6 P a g e Figure 7 SD Series Line Drawing if selected with optional breaker see Figure 9...
Страница 13: ...7 P a g e Figure 8 SD Series Line Drawing if selected with optional breaker see Figure 9 or Figure 10...
Страница 14: ...8 P a g e Figure 9 SD Series Line Drawing...
Страница 15: ...9 P a g e Figure 10 SD Series Line Drawing...
Страница 16: ...10 P a g e Figure 11 2XD Series Line Drawing...
Страница 80: ...74 P a g e Figure 36 SW1 in SD Systems...