ON-LINE RACK
PH 9360 - PH 9301 .
05: Activate / Deactivate ECO Mode Interface Phasak UPS PH 9360 / PH 9301
Parameter 2:
Enable or disable ECO function. You may choose
following two options:
DIS
: disable ECO function
ENA
: enable ECO function
If ECO function is disabled, voltage range and frequency range for ECO
mode still can be set, but it is meaningless unless the ECO function
is enabled.
06: Voltage range for ECO mode Interface Configuration
Parameter 1 & 2:
Setting acceptable voltage range for ECO mode.
You have to set up the range by setting high and low
points. When it shows “LLS” in parameter 2, please press “Enter” key and it
will show “LS” in parameter 1. Now, you can set up low
point in parameter 2 by pressing “Up” or “Down” key.
LS:
Low voltage point in ECO mode. The setting range is from 5% to 10%
of the nominal voltage.
Pressing “Enter” key to confirm the setting value for low point. Then, it will
show HS in parameter 1. Please set up high point in parameter 2 by
pressing “Up” or “Down” key.
HS:
High voltage point in ECO mode. The setting range is from 5% to 10%
of the nominal voltage.
07: Frequency range for ECO mode Interface Configuration
Parameter 1 & 2:
Setting acceptable frequency range for ECO mode.
You have to set up the range by setting high and low
points. When it shows “LLS” in parameter 2, please press “Enter”
key and it will show “LS” in parameter 1. Now, you can set up low point in
parameter 2 by pressing “Up” or “Down” key.
LS:
Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz. 60 Hz
system: Setting range is from 56.0Hz to 58.0Hz. The default
value is 48.0Hz/58.0Hz.
Pressing “Enter” key to confirm the setting value for low point. Then, it will
show HS in parameter 1. Please set up high point in parameter 2 by
pressing “Up” or “Down” key.
HS
: Set high frequency point for ECO mode. 50 Hz: Setting range is from
52.0Hz to 54.0 Hz. 60 Hz: Setting range is from 62.0Hz to 64.0Hz. The
default value is 52.0Hz/62.0Hz.
89 / 100