ON-LINE RACK
PH 9360 - PH 9301 .
03: Voltage range for bypass
Parameter 1 & 2:
Setting acceptable voltage range for bypass mode.
You have to set up the range by setting high and low
points. When it shows “LLS” in parameter 2, please press “Enter” key and
it will show “LS” in parameter 1. Now, you can set up low
point in parameter 2 by pressing “Up” or “Down” key.
LS:
Set the acceptable low voltage for bypass. Setting range is from
110V to 209V and the default value is 110V.
Pressing “Enter” key to confirm the setting value for low point. Then, it will
show HS in parameter 1. Please set up high point in parameter 2 by
pressing “Up” or “Down” key.
HS:
Set the acceptable high voltage for bypass. Setting range is
from
231V to 276V and the default value is 264V
.
Display
Configuration
04: Frequency range for the bypass Interface
Parameter 1 & 2:
Setting acceptable frequency range for bypass
mode. You have to set up the range by setting high and
low points. When it shows “LLS” in parameter 2, please press
“Enter” key and it will show “LS” in parameter 1. Now, you can set up low
point in parameter 2 by pressing “Up” or “Down” key.
LS:
Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 60 Hz
system: Setting range is from 56.0Hz to 59.0Hz. The default
value is 46.0Hz/56.0Hz.
Pressing “Enter” key to confirm the setting value for low point. Then, it will
show HS in parameter 1. Please set up high point in parameter 2 by
pressing “Up” or “Down” key.
HS:
Set the acceptable high frequency for bypass. 50 Hz: Setting range is
from 51.0Hz to 54.0 Hz. 60 Hz: Setting range is from 61.0Hz to 64.0Hz. The
default value is 54.0Hz/64.0Hz.