ON-LINE 1000VA / 2000VA / 3000VA
PH 9210 - PH 9220 - PH 9230 .
4. Storage and maintenance Phasak UPS
Intervention
The UPS contains non-reusable parts. The battery has a life of 3 ~ 5 years at 25 ° C
ambient temperature. When they have to be replaced, please contact their support
service.
Storage
If possible and for safety, charge the battery for 5 hours before storing it. Keep the UPS
protected and upright, in a dry, cool place.
During storage, charge the battery according to the following chart:
Storage Temperature
Charging frequency
Load Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours