PFT levelling pin / Safety, overview, operation and service
Operation
4.6
Table of faults
Fault
Possible cause
Troubleshooting
Tank and measuring scale not at the
same height
Mutual adjustment
Air bubbles in the measuring hose
Bleed the measuring hose
Insufficient measuring liquid in the tank
Top up measuring liquid
Filling or shut-off valve closed
Open filling or shut-off valve
Liquid column does
not settle after
pressing the self-
closing valve
Hole in the expansion tank blocked
Clear the rear hole on the expansion tank
Valve hose stuck in the measuring scale
Replace valve hose
Levelling pin does
not work after an
extended period at
a standstill
Measuring liquid has separated
Replace measuring liquid
Air bubbles in the hose
Bleed the levelling pin
Measurement
results differ from
previously deter-
mined measured
values
Measuring liquid has expanded due to
temperature fluctuations
Readjust the device
page 29 / 40