2. Intended use
With a danger and risk analysis, dangers created in the installation can be ascertained. If a dangerous situa-
tion is to be avoided, then the sounders can be used as an integral part of a technical safety system (Safety
Instrument System - SIS) up to safety integration level 2 (SIL 2).
Because of the very different integration of the sounders in various safety architectures, they must be
viewed differently. The following uses are described in the safety manual:
Use as a starting alarm of machines or similar applications (see section 4.4.1 )
Use as a warning system without automatic test function via a superior control (see section 4.4.2.1)
Use as a warning system with automatic test function via a superior control (see section 4.4.2.2 )
In general, the operational safety of the device and the therefore connected system is only guaranteed dur-
ing intended use in accordance with the specifications of the operating manual. Custom-designed dangers
could result from inappropriate or unintended use of this device.
3. Technical data
3.1. Installation drawing
143
1
33.5
15
0
Blanking plug M20
Fixing bolt e.g. 2x M6x20
M20x1,5
Ø7
Fig. 3
3.2. Electrical data
DS10
DS5
Nom. voltage
24V DC
24V DC
Voltage range
19V .. 29V
19V .. 29V
Current consumption
0,42A
0,28A
Current consumption monitoring circuit
20mA
Control current option TAS
<5mA (24V-)
Capacity of failure contact
Solid state relay
max. 230V~/80mA
R
DSON
<35
Ω
Duty cycle
100 %
Life time
A replacement of the device is recommended after 20 years or
2500 operating hours.