VersiStart i III
52
9.4.10
10 Display
10A – Language
Options:
English (default)
Português
Chinese Français
Español Italiano
Deutsch Russian
Description: Selects which language the keypad will use to display messages and feedback.
10B, 10C, 10D, 10E – User-Programmable Screen
Options:
Blank
Displays no data in the selected area, allowing long messages to be shown
without overlapping.
Starter State
The starter's operating state (starting, running, stopping or tripped). Only
available for top left and bottom left positions on the screen.
Motor Current
The average current measured on three phases.
Motor pf
The motor's power factor, measured by the soft starter.
Mains Frequency
The average frequency measured on three phases.
Motor kW
The motor's running power in kilowatts.
Motor HP
The motor's running power in horsepower.
Motor Temp
The motor's temperature, calculated by the thermal model.
kWh
The number of kilowatt hours the motor has run via the soft starter.
Hours Run
The number of hours the motor has run via the soft starter.
Description: Selects which information will be displayed on the programmable monitoring screen.
x
10B User Screen - Top Left
Default: Starter State
x
10C User Screen - Top Right
Default: Blank
x
10D User Screen - Bottom Left
Default: Hours Run
x
10E User Screen - Bottom Right
Default: Blank
10F – Graph Timebase
Options:
10 seconds (default)
10 minutes
30 seconds
30 minutes
1 minute
1 hour
5 minutes
Description: Sets the graph time scale. The graph will progressively replace the old data with new data.
10G – Graph Maximum
Range:
0% – 600%
Default:
400%
Description: Adjusts the upper limit of the performance graph.
10H – Graph Minimum
Range:
0% – 600%
Default:
0%
Description: Adjusts the lower limit of the performance graph.
10I – Mains Reference Voltage
Range: 100
–
690
V
Default:
400 V
Description: Sets the nominal mains voltage for the keypad's monitoring functions. This is used to calculate motor kilowatts and
kilovolt amperes (kVA) but does not affect the VersiStart i III's motor control or protection.
10J – Display A or kW
Options:
Current (default)
Motor kW
Description: Selects whether the VersiStart i III will display current (amperes) or motor kilowatts on the main monitoring screen.