VB230/400-6/25/30L (LP)
13
10.1 Environmental conditions
Note:
Please pay attention and consider for the operation of IE3 motors while
dimensioning of dc brakes the resulting higher starting currents.
For the use of IE3 motors we highly recommend to dimension and design
the needed braking devices one size higher.
11. Commissioning
The device is to be put into operation in 3 steps:
1. Mounting
2. Connection and
3. Parameter setting
11.1 Mounting instructions
Caution: Danger to life through electric shock!
The following conditions are to be complied with in order to ensure a safe
and reliable operation of the VersiBrake…-L (LP).
1. The device series VersiBrake…-L (LP) is to be used under overvoltage
conditions of the category III.
2. Make sure that pollution degree 2 or better, in accordance with IEC664, is
complied with.
3. The device is to be installed into a housing (min. degree of protection: IP54).
4. The device must be operated without being exposed to contamination by
water, oil, carbon deposits, dust, etc..
Warning:
Make sure that a minimum distance to adjoining devices is kept. Above and
underneath the housing a minimum distance of 50mm is to be kept.
Storage temperature
-25 ... 75°C
Operating temperature
0 ... 45°C
Degree of protection
- Enclosed version (w. housing):
- Circuit-board version:
IP 20
IP 00
Environment
Overvoltage category III, pollution degree 2
Weight
- Enclosed version (w. housing):
- Circuit-board version:
0.6kg
0.25kg