12. Commissioning
The device is to be put into operation in 3 steps:
1. Mounting
2. Connection and
3. Parameter setting
12.1 Mounting instructions
Caution: Danger to life through electric shock!
The following conditions are to be complied with in order to ensure a safe
and reliable operation of the VersiBrake…-L (LP).
1. The device series VersiBrake…-L (LP) is to be used under overvoltage
conditions of the category III.
2. Make sure that pollution degree 2 or better, in accordance with IEC664, is
complied with.
3. The device is to be installed into a housing (min. degree of protection: IP54).
4. The device must be operated without being exposed to contamination by
water, oil, carbon deposits, dust, etc..
Warning:
Make sure that a minimum distance to adjoining devices is kept. Above and
underneath the housing a minimum distance of 50mm is to be kept.
Please note, the total contact resistance on terminals X3 - X8 of the
connected contacts must not exceed 50 Ohm.
12.2 Connection
The braking device (with integrated motor contactor) is to be installed according to the attached
connection diagram. For other connections please consult PETER electronic GmbH & Co. KG.
Note:
Further connection proposals for special circuit arrangements are available
via our homepage at
www.peter-electronic.com
.
Note:
Prior to putting the motor brake into operation the wiring is to be checked.
Warning:
In the case of high-inertia starting, it may happen that the fuses blow.