background image

 

Pertronic Industries Ltd                                                                                            FAAST Power Supply Installation Note, Iss1.1 201501 

  Input Protection 

Internal 1 Amp slow blow fuse 

Specification (cont’d)

 

 

Output

 

  Nominal Output Voltage 

27.4 VDC ±1 % at 20 °C 

  Power Supply Charger Current  Current limited to 1.2 Amp 
  Maximum Short-Term Output 

2.5 Amp with 12 Amp-hour batteries fitted 

  Temperature Coefficient 

0.145 %/°C (set for battery charging) 

  Voltage Regulation 

0.13 % over full load at 20 °C 

 

Batteries

 

  Number and Type 

2 x 12 Volt AGM Valve-Regulated Lead-Acid 

 Capacity 

Maximum 

12 

Amp-hour 

 

General

 

  Mains Input Connector 

Termination block with an integral power switch 

  DC Output Connector 

Two-way terminal block 

  Defect Relay Output 

Change-over contact, 1 Amp @ 24 VDC 

  Internal Control 

Reset / Timer initialisation switch 

  Front Panel Indicator LEDs 

Mains (Green), Auto Test (Yellow), Battery Fault (Yellow) 

  Operating Temp. Range 

0 °C to 40 °C 

  Humidity 

10 % to 95 % (non-condensing)

 

 

Physical

 

  Dimensions 

230 x 350 x 120 (Height x Width x Depth mm) 

  Weight 

2.8 kg (excluding batteries) 

Mounting 

The power supply is designed to be wall-mounted. It should be mounted in a clean dry area with 
unobstructed natural convection between the unit and the wall. The cooling slots must not be restricted. Care 
must be taken to prevent reverse polarity connections between the power supply and load. 

Wiring Diagram 
 
 
 
 
 
 
 
 
 
 
 

 

Отзывы: