TESTING

Before testing, notify the proper authorities that the system is undergoing 
maintenance, and will temporarily be out of service. Disable the system to 
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing 
methods must satisfy the Authority Having Jurisdiction (AHJ). 
The sensor can be tested in the following ways:

A. Functional: Magnet Test (P/N M02-09-00)

 This sensor can be functionally tested with a test magnet. The test magnet
electronically simulates smoke in the sensing chamber, testing the sensor
electronics and connections to the control panel.
1.

 Hold the test magnet in the magnet test area as shown in Figure 3.

2.

The sensor should alarm the panel.

 Two LEDs on the sensor are controlled by the panel to indicate sensor 
status. Coded signals, transmitted from the panel, can cause the LEDs to 
blink, latch on, or latch off. Refer to the control panel technical documen-
tation for sensor LED status operation and expected delay to alarm.

B. Smoke Entry

 Sensitivity readings are available through the FACP. Refer to the manufac-
turer’s published instructions for proper use.
 Additionally, canned aerosol simulated smoke (canned smoke agent) may
be used for smoke entry testing of the smoke detector.
 When used properly, the canned smoke agent will cause the smoke detec-
tor to go into alarm. Refer to the manufacturer’s published instructions for
proper use of the canned smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary  
by manufacturer. Misuse or overuse of these products may have long term  
adverse effects on the smoke detector. Consult the canned smoke agent manu-
facturer’s published instructions for any further warnings or caution statements.

A sensor that fails any of these tests may need to be cleaned as described 
under CLEANING, and retested. 
When testing is complete, restore the system to normal operation and notify 
the proper authorities that the system is back in operation.

CLEANING

Before removing the detector, notify the proper authorities that the smoke 
detector system is undergoing maintenance and will be temporarily out of 
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1. Remove the sensor to be cleaned from the system.
2.  Remove the sensor cover by pressing firmly on each of the four removal

tabs that hold the cover in place. (See Figure 4.)

3.  Vacuum the screen carefully without removing it. If further cleaning is

required continue with Step 4, otherwise skip to Step 7.

4.  Remove the chamber cover/screen assembly by pulling it straight out.
5.  Use a vacuum cleaner or compressed air to remove dust and debris from

the sensing chamber.

6.  Reinstall the chamber cover/screen assembly by sliding the edge over the

sensing chamber. Turn until it is firmly in place.

7.  Replace the cover using the LEDs to align the cover and then gently push-

ing it until it locks into place.

8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
Note: Dispose of electronic waste according to national and local regulations 
when scrapping or replacing a device. Do not discard as general trash.

SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS

Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.

FIGURE 3: FEATURES OF THE PHOTO DETECTOR

Magnet 

Test 

Marker

LED

Base 

Alignment 

Notch

Magnet Test Marker

Base Alignment Notch

LED

 C2021-00

FIGURE 4: CLEANING THE PHOTO DETECTOR 

Cover 

Removal 

Tabs

Sensor Cover

Sensing Chamber 

Cover and Screen

Sensing Chamber 

 C2022-00

ON-SITE SENSITIVITY ADJUSTMENT

The sensitivity for this device is set at FDCIE.

For more information on sensitivity settings refer to the manufacturer's Fire
Alarm Control Panel manual.

 

Australian 
Standard

Lic. SMKH25312
SAI-Global

DEVICE AND SYSTEM SECURITY

Before installing this product ensure that the 
tamper seal on the packaging is present and 
unbroken and the product has not been tampered 
with since leaving the factory. Do not install this 
product if there are any indications of tampering. 
If there are any signs of tampering the product 
should be returned to the point of purchase.
It is the responsibility of the system owner to 
ensure that all system components, i.e. devices, 
panels, wiring etc., are adequately protected to 
avoid tampering of the system that could result 
in information disclosure, spoofing, and integrity 
violation.