WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the 
event of a fire.

Remove power from the communication line before installing sensors.

1.  Wire the sensor base (supplied separately) as shown in the wiring

diagram. (See Figure 2.)

2.  Set the desired address on the sensor address switches. (See Figure 1.)
3.  Install the sensor into the sensor base. Push the sensor into the base while

turning it clockwise to secure it in place.

4.  After all sensors have been installed, apply power to the control panel and

activate the communication line.

5.  Test the sensor(s) as described in the TESTING section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction.

FIGURE 2. WIRING DIAGRAM

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

Compatib

le

Control P

anel

CAUTION: Do not loop wire under 

terminal 1 or 2.  Break wire run to 

supervise connections.

CLOSE LOOP OPTIONAL WIRING

Remote 

Annunciator

(–)
(+)

RA

+

+

RA

+

+

RA

+

+

 

C0129-10AUS

TAMPER-RESISTANCE

Intelligent High-sensitivity Photoelectric smoke sensors include a tamper-re-
sistant capability that prevents their removal from the base without the use of 
a tool. Refer to the base manual for details on making use of this capability.

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Operating Current @ 24 VDC:  

300 uA (one communication every 5 seconds with green LED blink on communication)

Maximum Alarm Current:  

2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)

Maximum Current:  

4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range: 

-10°C to 50°C

Air Velocity: 

0 to 1219.2 m/min.

Height: 

51 mm installed in B501AUS-W/B501AUS-IV Base

Diameter: 

104 mm installed in B501AUS-W/B501AUS-IV Base

Weight: 

95 g

Isolator Load Rating:  

0.0063*

Applicable Standards:  

AS 7240.7 and NZS4512

*Please refer to your isolator base/module manual for isolator calculation instructions.

This sensor must be installed in compliance with the control panel system 
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). 

GENERAL DESCRIPTION

Model 7251CPI

 and 7251CPI-W

 

are

 plug-in type smoke sensor that combines a 

photoelectronic sensing chamber with addressable-analog communications 
providing  sensitivities from  0.02%  per  foot  to  2%  per  foot  obscuration  for 
Early Warning Fire Detection (EWFD) or Very Early Warning Fire Detection 
(VEWFD).
The  sensors  transmit  an  analog  representation  of  smoke  density  over  a 
com-munication line to a control panel. Rotary dial switches are provided 
for set-ting the sensor’s address. (See Figure 1.) 

FIGURE 1. ROTARY ADDRESS SWITCHES:

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

C0162-00

Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
An output is provided for connection to an optional remote LED annunciator  
(P/N RA100Z). 
Fire Alarm and Control panels offer different feature sets across different mod-
els.  As  a  result,  certain  features  of  the  photoelectric  sensors  may  be 
available  on  some  control  panels,  but  not  on  others.  7251CPI 

and 

7251CPI-W 

support  CLIP  (Classic  Loop  Interface  Protocol)  protocol  mode. 

The possible features available in the photoelectric sensors, if supported by 
the control panel are: 
1.  The sensor’s LEDs can operate in three ways—on, off, and blinking—and

they can be set to red, green, or amber. This is controlled by the panel.

2.  The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

3.  Devices are point addressable up to 1

5

9 addresses.

Please refer to the operation manual for the control panel for specific opera-
tion. The photoelectric sensors require compatible addressable communica-
tions to function properly. Connect these sensors to listed-compatible control 
panels only. 

Compatible bases:

 B501AUS-W/B501AUS-IV.

SPACING

 
 
 
 
 

 

Pertronic recommends spacing sensors in compliance with 

AS 1670.1:2015 or 

NZ4512. All detectors should be spaced and installed in accordance with the 
requirements of the relevant authority having jurisdiction. For specific infor

-

mation regarding sensor spacing, placement, and special applications, refer 
to AS 1670.1:2015, NZ4512, or the Smoke Detector Applica

tion Guide. 

I56-

7388

-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

7251CPI 

and 7251CPI-W

Intelligent High-sensitivity  

Photoelectric Smoke Sensors

www.pertronic.co.nz

www.pertronic.com.au

I56-

7388

-000 