Two LEDs on the sensor are controlled by the panel to indicate sensor 
status. Coded signals, transmitted from the panel, can cause the LEDs to 
blink, latch on, or latch off. Refer to the control panel technical 
documentation for sensor LED status operation and expected delay to 
alarm. 

B. Smoke Entry: Aerosol Generator (Gemini 501)    

The GEMINI model 501 aerosol generator can be used for smoke entry 
testing. Set the generator to represent 4%/ft to 5%/ft obscuration as de-
scribed in the GEMINI 501 manual. Using the bowl shaped applicator, 
apply aerosol until the panel alarms. Additionally, canned aerosol 
simulated smoke (canned smoke agent) may be used for smoke entry 
testing of the smoke detector. Tested and approved aerosol smoke 
products are the Smoke Detector Tester model 25S available from Home 
Safeguard Industries and Chekkit Smoke Detector Tester models 
CHEK02 and CHEK06 available from SDi. When used properly, the 
canned smoke agent will cause the smoke detector to go into alarm. 
Refer to the manufacturer’s published instructions for proper use of the 
canned smoke agent. 

 
 

 
Canned aerosol simulated smoke (canned smoke agent) formulas will 
vary by manufacturer. Misuse or overuse of these products may have 
long term adverse effects on the smoke detector. Consult the canned 
smoke agent manufacturer’s published instructions for any further 
warnings or caution statements. 

 

For 2251TMBPI, smoke entry testing should be performed immediately 
following the magnet test. Magnet test initiates an approximately 10 
minute period when the detector’s signal processing software routines 
are not active. Failure to first perform the magnet test will introduce a 
time delay before the detector alarms. 

C.  

Direct Heat Method (Hair Dryer of 1000-1500 watts) 2251TMBPI only

  

 

A hair dryer of 1000-1500 watts should be used to test the thermistors. 

Direct the heat toward either of the two thermistors, holding the heat 
source approximately 12 inches from the detector in order to avoid 
damaging the plastic housing. The detector will reset only after it has had 
sufficient time to cool. Make sure both thermistors are tested 
individually.  
A sensor that fails any of these tests should be cleaned as described 
under CLEANING, and retested. If the sensor fails after cleaning, it must 
be replaced. When testing is complete, restore the system to normal 
operation and notify the proper authorities that the system is back in 
operation. 

 
 
 

 
 
 
 

 

 

CLEANING 

Before removing the detector, notify the proper authorities that the smoke 
detector system is undergoing maintenance and will be temporarily out of 
service. Disable the zone or system undergoing maintenance to prevent 
un-wanted alarms. 
1. Remove the sensor to be cleaned from the system. 
2.  Remove the sensor cover by pressing firmly on each of the four 
removal tabs that hold the cover in place. 
3.  Vacuum the screen carefully without removing it. If further cleaning 
is required continue with Step 4, otherwise skip to Step 7. 
4.  Remove the chamber cover/screen assembly by pulling it straight out. 
5.  Use a vacuum cleaner or compressed air to remove dust and debris 
from the sensing chamber 
6.  Reinstall the chamber cover/screen assembly by sliding the edge over 
the sensing chamber. Turn until it is firmly in place. 
7.  Replace the cover using the LEDs to align the cover and then gently 
pushing it until it locks into place. Make sure that the thermistors do not 
become bent under the cover on 2251TMBPI model. 
8. Reinstall the detector. 
9. Test the detector as described in TESTING. 
10. Reconnect disabled circuits. 
11. Notify the proper authorities that the system is back on line. 
Note: Please dispose electronic waste following national or local 
regulations after being scrapped or replaced. Do not discard. 

FIGURE 4. SENSOR ASSEMBLY 

 

 
 
 
 
 
 
 
 
 
 
 
 

SPECIAL NOTE REGARDING SMOKE DETECTOR

 

GUARDS

 

Smoke detectors are not to be used with detector guards unless the 
combination has been evaluated and found suitable for that purpose. 

FCC Statement 

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. 

Note: This equipment has been tested and found to comply with the limits for a Class B digital devices, pursuant to Part 15 of the FCC Rules, These 
limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can 
radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio 
communications. However, there is no guarantee that interference will not occur in a particular installation, If this equipment does cause harmful 
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the 
interference by one or more of the following measures: 

 

Reorient or relocate the receiving measures. 

 

Increase the separation between the equipment and receiver. 

 

Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. 

 

Consult the dealer or an experienced radio/TV technician for help. 

 

THREE-YEAR LIMITED WARRANTY 

Pertronic Industries warrants its enclosed smoke detector to be free from 
defects in materials and workman-ship under normal use and service for a 
period of three years from date of manufacture. Pertronic Industries makes 
no other express warranty for this smoke detector. No agent, 
representative, dealer, or employee of the Company has the authority to 
increase or alter the obligations or limitations of this Warranty. The 
Company’s obligation of this Warranty shall be limited to the repair or 
replacement of any part of the smoke detector which is found to be 
defective in materials or workmanship under normal use and service 
during the three year period commencing with the date of manufacture. 
After contacting your local. Pertronic Industries representative for issuing 
a Return Authorization number (RA#) and arrange for return 

 

Return of the defective units. Please include a note describing the malfunction 
and suspected cause of failure. The Company shall not be obligated to 
repair or replace units which are found to be defective because of damage, 
unreasonable use, modifications, or alterations occurring after the date of 
manufacture. In no case shall the Company be liable for any consequential 
or incidental damages for breach of this or any other Warrant , expressed 
or implied whatsoever, even if the loss or damage is caused by the 
Company’s negligence or fault. Some states do not allow the exclusion or 
limitation of incidental or consequential damages, so the above limitation 
or exclusion may not apply to you. This Warranty gives you specific legal 
rights, and you may also have other rights which vary from state to state. 

 

 Ver. E 

SENSOR 
COVER

COVER

REMOVAL

TABS 

SENSING
CHAMBER

SENSING
CHAMBER 
COVER AND 
SCREEN 

CAUTION 

Отзывы: