8.4.
2.15 The cooling operation or heating operation does not operate.
Supposed causes
●
4-way valve faulty
Check of 4-way, please refer to part 5 in
9.5 Trouble Criterion Of Main Parts.
8.4.2.16 When cooling, heat exchanger of non-operating indoor unit frosts.
When heating, non-operating indoor unit get warm.
Supposed causes
●
EXV faulty
●
Wire and tubing connected in reverse.
Check of EXV, please refer to part 6 in
9.5 Trouble Criterion Of Main Parts.
Notice: If you replace outdoor main PCB of 1PAMSH27-MZO3-16, you need to check whether the PCB
isproduced before Apr. 2013. If yes, you need to short connect OLP connector., Otherwise, the
outdoorLED will
show “P0”.
Содержание 1PAMSH18-MZO2-16
Страница 3: ... Model 1PAMSH27 MZO3 16 W210 metal plate 113 Model 1PAMSH36 MZO4 16 W520 metal plate 128 ...
Страница 6: ...2 Suggested Indoor Unit Model Numbers ...
Страница 7: ......
Страница 9: ......
Страница 23: ...7 Wiring Diagrams 8 1 Wiring diagram of 1 drive 2 outdoor 1PAMSH18 MZO2 16 ...
Страница 24: ...PCB board of 1PAMSH18 MZ O2 16 ...
Страница 25: ...IPM board of 1PAMSH18 MZO2 16 ...
Страница 26: ......
Страница 27: ...8 2 Wiring diagram of 1 drive 3 outdoor 1PAMSH27 MZO3 16 ...
Страница 28: ......
Страница 29: ......
Страница 30: ...PCB board of 1PAMSH27 MZO3 16 ...
Страница 31: ...IPM board of 1PAMSH27 MZO3 16 ...
Страница 32: ...8 3 Wiring diagram of 1 drive 4 outdoor 1PAMSH36 MZO4 16 ...
Страница 33: ...PCB board of 1PAMSH36 MZO4 16 ...
Страница 34: ...IPM board of 1PAMSH36 MZO4 16 ...
Страница 35: ...PFC board of 1PAMSH36 MZO4 16 ...
Страница 36: ...8 4 Wiring diagram of 1 drive 5 outdoor ...
Страница 37: ......
Страница 71: ...IPM for dual tri zone IPM for qua zone P N for dual tri zone ...
Страница 72: ...P N for qua zone ...
Страница 73: ...bridge rectifier for dual tri zone bridge rectifier for qua zone ...
Страница 74: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V ...
Страница 76: ...Two ports of the inductance Inductance ...
Страница 77: ......
Страница 80: ...Vsp FG ...
Страница 82: ......
Страница 85: ......
Страница 88: ......
Страница 90: ......
Страница 103: ...6 EXV check Disconnect the connectors ...
Страница 104: ...Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50Ω Red Yellow Brown Orange Brown White ...
Страница 105: ...Red Blue Red Yellow ...
Страница 106: ...Brown Orange Brown White ...
Страница 121: ...Screws of front panel Screws of right rear panel Screws of top cover ...
Страница 129: ...Screws of big handle Screws of right rear panel Screws of water collector Screws of terminal board ...
Страница 136: ...Screws of front panel Screws of big handle Screws of right rear panel ...