6.3 Main Protection
6.3.1 Three Minutes Delay at restart for
compressor.
---- 1min delay for the 1
st
time start-up and 3
minutes delay for others.
6.3.2 Temperature protection of compressor
discharge.
When the compressor discharge temperature is
getting higher, the running frequency will be
limited as below rules:
----If 102
℃
(215.6
℉
)<T5<115
℃
(244.4
℉
),
decrease the frequency to the lower level every 2
minutes till to F1.
---If T5>115
℃
(244.4
℉
) for 10 seconds, the
compressor will stop and restart till T5<90
℃
(194
℉
).
6.3.3 Fan Speed is out of control (DC fan
motor).
---- When outdoor fan speed is lower than
300RPM or higher than 2400RPM for 60 second,
the whole unit stops and LED displays failure.
6.3.4 Inverter module Protection.
----Inverter module protection itself has a
protection function against current, voltage and
temperature. If these protections happened, the
corresponding code will display on indoor unit
LED and A/C will stop. The unit will recover 3min
delay after the protection disappeared.
6.3.5 Low voltage protection
VOLT_RST1_ADD
VOLTAGE
No limit
VOLT_LTM1_ADD
VOLT_RST2_ADD
VOLT_LTM2_ADD
VOLT_LTM_FREQ1_ADD
VOLT_LTM_FREQ2_ADD
Note: if the low voltage protection occurs and not
resumes within 3min, it will keep the protection
always after restart the machine.
6.3.6 Compressor current limit protection
If the compressor current exceeds the current
limit value for 10 seconds, the compressor
frequency will be limited as below table.
Cooling mode:
Current
frequency(Hz)
Current limit
value(A)
Frequency limit
COOL_F16
ICOOLLMT12 Decrease the frequency to
COOL_F4 and run at COOL_F4
for 3 minutes.
After that, the frequency will be
adjusted according to the capacity
demand and rise to the upper
level every 3 minutes
(When the frequency>COOL_F4
via capacity demand).
COOL_F15
ICOOLLMT11
COOL_F14
ICOOLLMT10
COOL_F13
ICOOLLMT9
COOL_F12
ICOOLLMT8
COOL_F11
ICOOLLMT7
COOL_F10
ICOOLLMT6
COOL_F9
ICOOLLMT5
COOL_F8
ICOOLLMT4
COOL_F7
ICOOLLMT3
COOL_F6
ICOOLLMT2
COOL_F5
ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will
not be limited.
After 10s of the compressor start, if the current>ICOOL, the AC will
display the failure for 30 seconds and stop. The AC will restart 3
minutes later.
Heating mode:
Current
frequency(Hz)
Current limit
value(A)
Frequency limit
HEAT_F16
IHEATLMT12
Decrease the frequency to
HEAT_F4 and run at HEAT_F4 for
3 minutes.
After that, the frequency will be
adjusted according to the capacity
demand and rise to the upper
level every 3 minutes
(When the frequency>Heat_F4 via
capacity demand).
HEAT_F15
IHEATLMT11
HEAT_F14
IHEATLMT10
HEAT_F13
IHEATLMT9
HEAT_F12
IHEATLMT8
HEAT_F11
IHEATLMT7
HEAT_F10
IHEATLMT6
HEAT_F9
IHEATLMT5
HEAT_F8
IHEATLMT4
HEAT_F7
IHEATLMT3
HEAT_F6
IHEATLMT2
HEAT_F5
IHEATLMT1
Содержание 1PAMSH18-MZO2-16
Страница 3: ... Model 1PAMSH27 MZO3 16 W210 metal plate 113 Model 1PAMSH36 MZO4 16 W520 metal plate 128 ...
Страница 6: ...2 Suggested Indoor Unit Model Numbers ...
Страница 7: ......
Страница 9: ......
Страница 23: ...7 Wiring Diagrams 8 1 Wiring diagram of 1 drive 2 outdoor 1PAMSH18 MZO2 16 ...
Страница 24: ...PCB board of 1PAMSH18 MZ O2 16 ...
Страница 25: ...IPM board of 1PAMSH18 MZO2 16 ...
Страница 26: ......
Страница 27: ...8 2 Wiring diagram of 1 drive 3 outdoor 1PAMSH27 MZO3 16 ...
Страница 28: ......
Страница 29: ......
Страница 30: ...PCB board of 1PAMSH27 MZO3 16 ...
Страница 31: ...IPM board of 1PAMSH27 MZO3 16 ...
Страница 32: ...8 3 Wiring diagram of 1 drive 4 outdoor 1PAMSH36 MZO4 16 ...
Страница 33: ...PCB board of 1PAMSH36 MZO4 16 ...
Страница 34: ...IPM board of 1PAMSH36 MZO4 16 ...
Страница 35: ...PFC board of 1PAMSH36 MZO4 16 ...
Страница 36: ...8 4 Wiring diagram of 1 drive 5 outdoor ...
Страница 37: ......
Страница 71: ...IPM for dual tri zone IPM for qua zone P N for dual tri zone ...
Страница 72: ...P N for qua zone ...
Страница 73: ...bridge rectifier for dual tri zone bridge rectifier for qua zone ...
Страница 74: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V ...
Страница 76: ...Two ports of the inductance Inductance ...
Страница 77: ......
Страница 80: ...Vsp FG ...
Страница 82: ......
Страница 85: ......
Страница 88: ......
Страница 90: ......
Страница 103: ...6 EXV check Disconnect the connectors ...
Страница 104: ...Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50Ω Red Yellow Brown Orange Brown White ...
Страница 105: ...Red Blue Red Yellow ...
Страница 106: ...Brown Orange Brown White ...
Страница 121: ...Screws of front panel Screws of right rear panel Screws of top cover ...
Страница 129: ...Screws of big handle Screws of right rear panel Screws of water collector Screws of terminal board ...
Страница 136: ...Screws of front panel Screws of big handle Screws of right rear panel ...