INSTALLATION INSTRUCTIONS

(Continued)

WIRING DIAGRAM

Make sure that the color of the wires in the outdoor unit and terminal No. are the same as those of the indoor unit.

  The diagram is reference only, and the actual terminal shall prevail.

1. 208/230V

2. 115V

INSTALLATION INSTRUCTIONS

(Continued)

Manifold Gauge

Compound gauge

-76cmHg

Low pressure valve

 

High pressure valve

 

Charge hose

Vacuum pump

Pressure gauge

Fig. 9.1

START-UP

TEST OPERATION

Perform test operation after completing gas leak 

and electrical safety check.

   Turn on electrical disconnect to outdoor unit.
   Push the “ON/OFF” button on Remote 

Controller to begin testing.

   Push MODE button, select COOLING, 

HEATING, FAN mode to confirm all functions.

SYSTEM CHECKS

   Conceal refrigerant pipes where possible.
   Make sure drain hose slopes downward along 

entire length.

   Ensure all refrigerant pipes and connections 

are properly insulated.

  Fasten pipes to outside wall, when possible.
   Seal and weatherproof wall hole which the 

interconnecting wires and refrigerant pipes 

pass through.

INDOOR UNIT

   Do all Remote controller’s buttons function 

properly?

   Do the display panel lights work properly?
  Does the swing louver function properly?
  Does the drain work?

OUTDOOR UNIT

   Push the mode button to COOL and adjust the 

room setting to 61°F (16°C) deg. wait up to 3 

minutes from compressor time guard. Does 

compressor and outdoor fan turn on in cooling 

mode?

   Push the mode button to HEAT and adjust 

the room setting to 85°F(30°C) deg. wait up to 

3 minutes for compressor time guard. Does 

compressor and outdoor fan turn on in heat 

mode?

EVACUATION INSTRUCTIONS

Before using a manifold gauge and a vacuum 

pump, read their operation manuals to make sure 

you know how to use them properly.

   Using a valve core removal tool with a micron 

gauge port attach it to the low side valve 

and remove the valve core. Then attach your 

micron gauge to the appropriate port.

   Connect the manifolds low side hose (blue) to 

the other end of the valve core removal tool

   Open the Low Pressure side of the manifold 

gauge. Keep the High Pressure side closed.

  Turn on the vacuum pump to evacuate the system.
   Run the vacuum pump until your Micron Gauge 

reads 400 microns

   Isolate the valve core removal tool and watch if 

the pressure rises: if it rises over 500 microns 

keep running the vacuum. The goal is to stabilize 

with no rise in pressure and stay at 500 microns

   After you have achieved a proper vacuum 

open the valves on the condenser using a 

5 mm allen wrench turning them counter 

clockwise until it stops

OPEN VALVE STEMS GENTLY

 

When opening the valve stems, turn the 

hexagonal wrench until it hits against the stopper. 

DO NOT try to force the valve to open further.

   Replace the schrader valve back into the low 

side service port. You are now finished with a 

proper vacuum and you can remove your hoses.

  Tighten valve caps by hand, then tighten it 

completely using an adjustable wrench.

Содержание 3PAMSH30B-SZO

Страница 1: ...SINGLE ZONE DUCTLESS MINI SPLIT SYSTEM OWNER S MANUAL MODELS 3PAMSH30B SZW 3PAMSH30B SZO 3PAMSH36B SZW 3PAMSH36B SZO ...

Страница 2: ...remote electric power supplies before servicing The best length of the connecting pipe between the indoor unit and outdoor unit is less than 24 6ft 7 5 meters It will affect the efficiency of the air conditioner if the distance longer than that length This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and ...

Страница 3: ...NCE This marking indicates that this product should not be disposed with other household wastes throughout the North America To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where th...

Страница 4: ...EEDED BE SURE TO MAKE ALL FLARES WITH AN APPROVED 410A FLARING TOOL A MINIMUM OF 10 FT LINE SET IS REQUIRED ON SINGLE ZONE IF LINE SET IS LONGER THAN 25 FT YOU WILL NEED TO WEIGH IN THE RECOMMENDED AMOUNT OF REFRIGERANT SEE INSTALLATION AND OPERATION MANUAL ON MULTI ZONE THERE IS ENOUGH REFRIGERANT FOR 25 FT OF LINE SET PER ZONE EXAMPLE 3 ZONE 75 FT OF LINE SET USE OIL OR NYLOG ON THE THREADS AND ...

Страница 5: ...more than 24 6ft 7 5m the refrigerant should be charged additionally according to below table model required amount of additional refrigerant oz ft 9K 18K 0 22 24K 0 32 30K 36K 0 43 Indoor unit Outdoor unit Indoor unit is higher than outdoor unit Pipe length is 65 4ft 20m Max Height should be less than 32 8ft 10m Indoor unit Outdoor unit Outdoor unit is higher than indoor unit Pipe length is 65 4f...

Страница 6: ...mum of six screws evenly spaced to properly support indoor unit weight NOTE The shape of your mounting plate may be different from the one above but the installation method is similar NOTE As the above figure shown the six holes matched with tapping screw on the mounting plate must be used to fix the mounting plate the others are prepared MOUNTING PLATE INSTRUCTIONS ON WOODEN WALL INSTALLATION INS...

Страница 7: ...he drain hose Then connect the power cords After connecting wrap the piping cords and drain hose together with thermal insulation materials NOTE Dimensions are in inch unless otherwise stated in the table INSTALLATION INSTRUCTIONS Continued PIPING JOINTS THERMAL INSULATION Wrap the piping joints with thermal insulation materials and then wrap with a vinyl tape PIPING THERMAL INSULATION a Place the...

Страница 8: ...g floor If installed on the wall or roof make sure to fix the supporter well to prevent it from shaking due to serious vibration or strong wind Service Valve Cover PIPE DIAMETER NUT SIZE TIGHTENING TORQUE INCH MM INCH MM FT LBS 1 4 6 35 1 4 17 11 to 15 3 8 9 5 3 8 22 22 to 26 1 2 12 7 1 2 25 37 to 41 5 8 15 9 5 8 29 44 to 48 3 4 19 3 4 32 52 to 55 NOTE Over tightening may damage flare connections ...

Страница 9: ...ressor and outdoor fan turn on in cooling mode Push the mode button to HEAT and adjust the room setting to 85 F 30 C deg wait up to 3 minutes for compressor time guard Does compressor and outdoor fan turn on in heat mode EVACUATION INSTRUCTIONS Before using a manifold gauge and a vacuum pump read their operation manuals to make sure you know how to use them properly Using a valve core removal tool...

Страница 10: ...ive device may trip and stop the appliance For some models can keep cooling at 5 F 15 C outdoor ambient via unique design Normally optimum cooling performance will be achieved above 70 F 21 C Please consult the merchant to get more information For some models can keep heating at 5 F 15 C outdoor ambient some models heat at 4 F 20 C outdoor ambient even heat at lower outdoor ambient The temperature...

Страница 11: ...ble for a few minutes when you come home the unit will have the room back to your desired temperature in no time DON T FORGET THE FAN The fan is much like a car The faster it runs the more energy is consumed Sometimes we need the car to go fast but slow is good enough most of the time Try saving money by using the comfortable quiet low fan speed as much as possible TROUBLESHOOTING PROBLEM SOLUTION...

Страница 12: ...ours of usage as reminder to clean the filter After filter cleaning press the filter reset button located on the indoor unit behind the front panel in order to reset the display optional Running indicator It lights up when the AC is running It flashes during defrosting Timer indicator It lights up during set time Sleep indicator It lights up in sleep mode To let the AC run or stop by pressing the ...

Страница 13: ...844 4PA AIRE 844 472 2473 support perfectaire us CANADA SUPPORT 877 997 2473 supportcanada perfectaire us www perfectaire us 5401 Dansher Road Countryside IL 60525 Printed in China 1121_M868 ...

Отзывы: