Perfect Aire 1PAMSH09-SZO-14.5 Скачать руководство пользователя страница 9

Installation Instructions

 

(cont.)

-8-

IMPORTANT: See pages 3 

 4 of this manual for instructions regarding the outdoor unit's installation location.

1. Outdoor Unit Installation Precautions

•  Install the outdoor unit on a rigid base to prevent increased noise level and vibration.
•  Determine the air outlet direction where the discharged air is not blocked.
•  In the case that the installation place is exposed to strong wind such as seaside, make sure the fan operates properly 

by putting the unit lengthwise along the wall or using a dust or shield plate.

•  The connection between the bracket and the wall and that between the bracket and the air conditioner should be firm, 

stable, and reliable.

•  In windy areas, install the unit to prevent the admission of 

wind. If suspending installation is required, the installation 

bracket should be in accordance with technical requirements 

in the installation bracket diagram. The installation wall should 

be solid brick, concrete, or the same intensity of construction, 

or the installer should take action to reinforce it.

•  Be sure there are no obstacles blocking air radiating from the unit.

2. Drain Joint Installation

NOTE:

 The drain joint will differ slightly based on the model being installed.

•  For the drain joint with the seal (Fig 14A), first fit the seal onto the drain joint, then 

insert the drain joint into the base pan hole of outdoor unit. Rotate 90º to securely 

assemble them. 

•  To install drain joint as shown in Figure 14B, insert the drain joint into the base pan 

hole of outdoor unit until it remains fixed with a clicking sound. Connecting the drain 

joint with an extension drain hose (purchased locally) in case the water drains of the 

outdoor unit during the heating mode.

Outdoor Unit Installation

Seal

Drain joint

Base pan hole

of outdoor unit

(A)

(B)

Fig. 14

Fig. 13

Strong 

wind

Strong 

wind

Barrier 

Incorrect

Correct

3. Refrigerant Pipe Connection

Flaring

•  Cut the cooper tube with a pipe cutter. Clean and remove any burrs from 

the end of the pipe.

•  Remove the flare nuts attached to the indoor and outdoor unit. Slide the 

nuts on the copper tube.

•  Insert copper tube into a flaring block and use the table to the right to 

determine how much tube should be above the black before flaring the 

tube. You can also figure the thickness of a nickel to use as a standard.

Tightening Connection

•  Align the tube to the proper connections on the indoor and outdoor units.
•  Sufficiently tighten the flare nut with fingers and then tighten it with a 

crescent wrench and torque wrench as shown in Figure 15.

•  Excessive torque can break nut depending on installation connections.

Bar

Copper pipe

Clamp handle

Handle

Bar

"A

"

Indoor unit tubing

Flare nut Pipings

Oblique Roughness Burr

O

90

Fig. 15

Outer 

Diameter (in.)

A (in.)

Max.

Min.

Φ 1/4"

0.052

0.03

Φ 3/8"

0.063

0.04

Φ 1/2"

0.071

0.04

Φ 5/8"

0.087

0.079

Outer Diameter. 

(in.)

Tightening Torque 

(N.cm)

Additional Tightening 

Torque (N.cm)

Φ 1/4"

1500 (153 kgf.cm)

1600 (163 kgf.cm)

Φ 3/8"

2500 (255 kgf.cm)

2600 (265 kgf.cm)

Φ 1/2"

3500 (357 kgf.cm)

3600 (367 kgf.cm)

Φ 5/8"

4500 (459 kgf.cm)

4700 (479 kgf.cm)

Содержание 1PAMSH09-SZO-14.5

Страница 1: ...e read this manual carefully and keep it for future reference along with your receipt SINGLE ZONE DUCTLESS MINI SPLIT SYSTEM INSTALLATION MANUAL INDOOR UNIT 1PAMSH09 SZW 14 5 1PAMSH09 SZW 15 1PAMSH12 SZW 15 1PAMSH18 SZW 15 OUTDOOR UNIT 1PAMSH09 SZO 14 5 1PAMSH09 SZO 15 1PAMSH12 SZO 15 1PAMSH18 SZO 15 ...

Страница 2: ... a chart with solutions to the most common problems Referring to this section may save time and prevent the need for a service call in the event of a problem Safety Precautions Installation Precautions 2 Warning 2 Caution 2 Installation Instructions Selecting installation location 3 4 Accessories 4 Indoor unit installation 5 7 Outdoor unit installation 8 9 Air Purging and Test Operation Air Purgin...

Страница 3: ...efective incorrect installation can result in water leakage electrical shock or fire 2 Install the indoor unit per these instructions Make sure it is secured properly to the wall If not installed properly the unit could drop or fall causing injury 3 An independent circuit breaker must be used for each indoor unit If the circuit breaker is not sized properly electrical shock and or a fire can resul...

Страница 4: ...irect sunlight or rain exposure make sure that heat radiation from the condenser is not restricted Do not place animals and plants in the path of the air inlet or outlet Refer to Fig 1 which notes the amount of space there must be between the unit and any walls ceiling fences and other obstacles items Install the outdoor unit on concrete or plastic pad or mount to a wall with the proper brackets s...

Страница 5: ...ping Screw A ST3 9x25 5 8 depends on model 4 Seal for cooling heating models only 1 5 Drain Joint for cooling heating models only 1 6 Connecting pipe assembly Liquid side Φ 1 4 6 35 mm Parts you must purchase The pipe size differs from appliance to appliance Consult the technician for the proper size Φ 3 8 9 52 mm Gas side Φ 3 8 9 52 mm Φ 1 2 12 7 mm Φ 5 8 16 mm 7 Remote control 1 8 Self tapping S...

Страница 6: ... wall with five or eight type A screws NOTE Mount the Installation Plate and drill holes in the wall according to the wall structure and corresponding mounting points on the installation plate The Installation Plate provided with the machine differs based on the model being installed All units are in inches unless otherwise noted Correct orientation of Installation Plate Right rear side refrigeran...

Страница 7: ...nit All wiring must comply with local and national codes and be installed by a certified electrician Suggested Minimum Wire Size AWG American Wire Gauge Appliance Amps AWG Wire Size 10 18 13 16 18 14 25 12 30 10 NOTE The cable size and the current of the fuse or switch are determined by the maximum current indicated on the nameplate which is located on the side panel of the unit Please refer to th...

Страница 8: ...staller in case of water leakage Bundle the tubing connecting cable and drain hose with tape securely and evenly as shown in the figures on the right NOTE Because the condensed water from rear of the indoor unit is gathered in the drain pan and is piped out of the room do not put anything else in the drain pan CAUTION Connect the indoor unit first then the outdoor unit Be careful not to let the dr...

Страница 9: ...l drain joint as shown in Figure 14B insert the drain joint into the base pan hole of outdoor unit until it remains fixed with a clicking sound Connecting the drain joint with an extension drain hose purchased locally in case the water drains of the outdoor unit during the heating mode Outdoor Unit Installation Seal Drain joint Base pan hole of outdoor unit A B Fig 14 Fig 13 Strong wind Strong win...

Страница 10: ...ach tube both liquid and gas side tubes between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed Pipe length and refrigerant amount indicated in the chart below Connective pipe length Air purging method Additional amount of refrigerant to be charged Less than 16 4 ft Use vacuum pump More than 16 4 ft Use vacuum pump 9k 12k 18k Liquid side...

Страница 11: ...onnections and outdoor unit connections using a soft brush to check for leakage of the connecting points of the piping If bubbles come out this indicates that the pipes have leakage Leak detector Use the leak detector to check for leakage CAUTION See Figure 20 A Lo packed valve B Hi packed valve C and D are ends of indoor unit connection Test Running Perform test operation after completing gas lea...

Страница 12: ...BUILT TO LAST Distributed by Perfect Aire LLC 5151 Belt Line Rd Suite 878 Dallas TX 75254 Specification and performance data is subject to change without notice Printed in China 877 365 6274 www perfectaire us ...

Отзывы: